Housing Provisions clause · ABCB Housing Provisions 2025

10.2.15 Stepdown showers

Part 10.2 Wet area waterproofing

Open 10.2.15 on NCC Online ↗

For stepdown showers, the highest finished floor level of the shower area must be stepped down a minimum of 25 mm lower than the finished floor level outside the shower (see Figures 10.2.15a, 10.2.15b, 10.2.15c and 10.2.15d).

Figure 10.2.15a Typical enclosed stepped down shower construction (membrane below tile bed)

Figure 10.2.15b Typical enclosed stepped down shower construction (membrane above tile bed)

Figure 10.2.15c Typical unenclosed stepped down shower construction (membrane below tile bed)

Figure 10.2.15d Typical unenclosed stepped down shower construction (membrane above tile bed)

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 10.2.15.