Housing Provisions clause · ABCB Housing Provisions 2025

10.2.2 Shower area (enclosed and unenclosed)

Part 10.2 Wet area waterproofing · NCC 2019: Table 3.8.1.1

Open 10.2.2 on NCC Online ↗

(1) For a shower area with a hob, step-down or level threshold, the following applies:

The floor of the shower area must be waterproof, including any hob or step-down (see Figure 10.2.2); and

The walls of the shower area must be waterproof not less than 1800 mm above the floor substrate (see Figure 10.2.2).

Wall junctions and joints within the shower area must be waterproof (see Figure 10.2.2).

Wall/floor junctions within the shower area must be waterproof (see Figure 10.2.2).

Penetrations within the shower area must be waterproof.

(2) A shower with a preformed shower base must also comply with the requirements of (1), except for (a) which is not applicable.

Figure 10.2.2 Extent of treatment for shower areas — concrete compressed fibre-cement and fibre-cement sheet floors

Figure Notes

Wall/floor junction heights are to be as per 10.2.2 to 10.2.6 (as applicable).

Notes

Where a shower is above a bath or spa, use requirements for shower.

Changed since NCC 2022. See ABCB Housing Provisions 2022 10.2.2, or show what changed.

(1) For a shower area with a hob, step-down or … junctions and joints within the shower area must be waterproof not less than 40 mm either side of the junction (see Figure 10.2.2). Wall/floor junctions within the shower area must … is above a bath or spa, use requirements for shower.

Removed words are struck through; added words are highlighted. Comparison of the text only.