Housing Provisions clause · ABCB Housing Provisions 2025

10.7.4 Services

Part 10.7 Sound insulation · NCC 2019: 3.8.6.5

Open 10.7.4 on NCC Online ↗

(1) Services must not be chased into concrete or masonry separating walls.

(2) If a duct, soil, waste, water supply or stormwater pipe is located in a separating wall —

a door or panel providing access to a duct or pipe required to be separated must—

not open into any habitable room, other than a kitchen; and

in any other part must be firmly fixed so as to overlap the frame or rebate of the frame by not less than 10 mm and be constructed of—

wood, plasterboard or blockboard not less than 33 mm thick; or

compressed fibre reinforced cement sheeting not less than 9 mm thick; or

other suitable material with a mass per unit area not less than 24.4 kg/m2; and

in the case of a water supply pipe, it must—

only be installed in discontinuous construction; and

in the case of a water supply pipe that serves one dwelling, not be fixed to the wall leaf on the side of any other dwelling and have a clearance not less than 10 mm to the other wall leaf.

(3) Electrical outlets must be offset from each other—

in masonry walling, not less than 100 mm; and

in timber or steel-framed walling, not less than 300 mm.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 10.7.4.

Defined terms used