10.7.8 Acceptable forms of construction for timber and steel framed walls
Part 10.7 Sound insulation · NCC 2019: Table 3.8.6.1d
(1) Acceptable forms of construction for timber and steel framed walls are set out in (2) and (3).
(2) Two rows of 90 mm x 35 mm timber studs or two rows of 64 mm steel studs at 600 mm centres with—
an air gap not less than 20 mm between the rows of studs; and
50 mm thick glass wool insulation or 60 mm thick polyester insulation with a density of 11 kg/m³, positioned between one row of studs, and
two layers of 13 mm fire protective grade plasterboard or one layer of 6 mm fibre cement sheet and one layer of 13 mm fire protective grade plasterboard, fixed to outside face of studs,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.8a.
(3) Two rows of 64 mm steel studs at 600 mm centres with—
an air gap not less than 80 mm between the rows of studs; and
200 mm thick polyester insulation with a density of 14 kg/m3 positioned between studs; and
one layer of 13 mm fire-protective grade plasterboard and one layer 13 mm plasterboard on one outside face and one layer of 13 mm fire-protective grade plasterboard on the other outside face,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.8b.
Figure 10.7.8a Two rows of 90 mm x 35 mm timber studs or two rows of 64 mm steel studs at 600 mm centres
Figure 10.7.8b Two rows of 64 mm steel studs at 600 mm centres
Changed since NCC 2022 (minor wording). See ABCB Housing Provisions 2022 10.7.8, or show what changed.
(1) Acceptable forms of construction for timber and steel framed … 35 mm timber studs or two rows of 64 mm steels steel studs at 600 mm centres with — an air gap … 35 mm timber studs or two rows of 64 mm steels steel studs at 600 mm centres Figure 10.7.8b Two rows of 64 mm steel studs at 600 mm centres
Removed words are struck through; added words are highlighted. Comparison of the text only.