Housing Provisions clause · ABCB Housing Provisions 2025

10.8.2 Exhaust systems

Part 10.8 Condensation management · NCC 2019: 3.8.7.3

Open 10.8.2 on NCC Online ↗

(1) An exhaust system installed in a kitchen, bathroom, sanitary compartment or laundry must have a minimum flow rate of—

25 L/s for a bathroom or sanitary compartment; and

40 L/s for a kitchen or laundry.

(2) Exhaust from a kitchen, kitchen range hood, bathroom, sanitary compartment or laundry must discharge directly or via a shaft or duct to outdoor air.

(3) Where a venting clothes dryer is installed, it must discharge directly or via a shaft or duct to outdoor air.

(4) An exhaust system that is not run continuously and is serving a bathroom or sanitary compartment that is not ventilated in accordance with 10.6.2(a) must—

be interlocked with the room’s light switch; and

include a run-on timer so that the exhaust system continues to operate for 10 minutes after the light switch is turned off.

(5) Except for rooms that are ventilated in accordance with 10.6.2(a), a room with an exhaust system in accordance with (1) must be provided with make-up air—

via openings to an adjacent room with a free area of 14,000 mm2; or

in accordance with AS 1668.2.

(6) Except for rooms that are ventilated in accordance with 10.6.2(a), a room with an exhaust system in accordance with (3) must be provided with make-up air in accordance with AS 1668.2.