10.8.4 Ventilation of a roof space with the primary insulation layer parallel to the roof plane

Part 10.8 Condensation management

Open 10.8.4 on NCC Online ↗

(1) In climate zones 6, 7 and 8, a roof system with the primary insulation layer installed parallel to the roof plane must have a roof space that—

is located immediately above—

the primary insulation layer; or

any control layer installed immediately above the primary insulation layer; and

is not obstructed by insulation; and

has a height not less than 18 mm as measured perpendicular to the plane of the roof; and

for roofs less than 10 m2, is ventilated to outdoor air through openings not less than—

7,000 mm2/m provided at the eaves or low level; and

5,000 mm2/m at the high level or ridge; and

for all other roofs, is ventilated to outdoor air through openings not less than—

20,000 mm2/m provided at the eaves or low level; and

5,000 mm2/m at the high level or ridge.

(2) Where a control layer is installed immediately above the primary insulation layer in climate zones 6, 7 and 8, it must have a vapour permeance of not less than 1.14 μg/N.s.

(3) The requirements of (1) do not apply to a—

concrete roof; or

roof that is made of insulated sandwich panels with or without an additional ceiling lining; or

roof that is subject to Bushfire Attack Level FZ requirements in accordance with AS 3959; or

tiled roof without a control layer located above the primary insulation layer.