11.2.2 Stairway construction

Part 11.2 Stairway and ramp construction · NCC 2019: 3.9.1.2

Open 11.2.2 on NCC Online ↗

(1) A stairway must be designed to take loading forces in accordance with AS/NZS 1170.1 and must have—

not more than 18 and not less than 2 risers in each flight; and

goings (G), risers (R) and a slope relationship quantity (2R + G) in accordance with Table 11.2.2a, except as permitted by (2) and (3); and

constant goings and risers throughout each flight, except as permitted by (3) and (4), and the dimensions of goings (G) and risers (R) in accordance with (1), (2) and (3) are considered constant if the variation between—

adjacent risers, or between adjacent goings, is not more than 5 mm; and

the largest and smallest riser within a flight, or the largest and smallest going within a flight, is not more than 10 mm; and

risers which do not have any openings that would allow a 125 mm sphere to pass through between the treads; and

treads of solid construction (not mesh or other perforated material) if the stairway is more than 10 m high or connects more than 3 storeys.

(2) In the case of a stairway serving only non-habitable rooms, such as attics, storerooms and the like that are not used on a regular or daily basis—

the going (G), riser (R) and slope relationship quantity (2R + G) in accordance with Table 11.2.2a may be substituted with those in Table 11.2.2b; and

need not comply with (1)(d).

(3) In the case of a stairway with winders —

a maximum of 3 consecutive winders in lieu of a quarter landing in a flight and a maximum of 6 consecutive winders in lieu of a half landing in a flight; and

the going (G) of all winders in lieu of a quarter or half landing may vary from the going of the straight treads within the same flight provided that the going (G) of such winders is constant.

(4) The point of measurement of the going (G) in the slope relationship quantity (2R + G) for tapered treads and treads in spiral stairways as described in Table 11.2.2a (see Figure 11.2.2a, Figure 11.2.2b and Figure 11.2.2c) must be—

for tapered treads, other than treads in a spiral stairway —

not more than 1 m in width, the middle of the unobstructed width of the stairway (see Figure 11.2.2b); and

more than 1 m in width, 400 mm from the unobstructed width of each side of the stairway (see Figure 11.2.2c); and

for treads in spiral stairways, the point seven tenths of the unobstructed width from the face of the centre pole or support towards the handrail side (see Figure 11.2.2d and Figure 11.2.2e).

(5) Riser and going dimensions must be measured in accordance with Figure 11.2.2f.

Table 11.2.2a Riser and going dimensions (mm)

Stair type

Riser (R) (see Figure 11.2.2f)

Going (G) (see Figure 11.2.2f)

Slope relationship (2R+G)

Max

Min

Max

Min

Max

Min

Stairs (other than spiral)

190

115

355

240

700

550

Spiral

220

140

370

210

680

590

Table Notes

Riser and going dimensions must be measured in accordance with Figure 11.2.2f

Table 11.2.2b Riser and going dimensions (mm) — stairways serving non-habitable rooms used infrequently

Riser (R)

Going (G)

Slope relationship (2R+G)

Max

Min

Max

Min

Max

Min

225

130

355

215

700

540

Table Notes

The going (G) must be not more than the tread depth plus a maximum gap of 30 mm between the rear edge of one tread and the nosing of the tread above.

Figure 11.2.2a Measurement of slope relationship — Plan view — Stair with 2 flights

Figure 11.2.2b Measurement of slope relationship — Plan view — Tapered treads not more than 1 m wide

Figure 11.2.2c Measurement of slope relationship — Plan view — Tapered treads more than 1 m wide

Figure 11.2.2d Spiral stairs — Measurement for slope relationship

Figure 11.2.2e Spiral stairs — Measurement of openings in stairs

Figure 11.2.2f Riser and going dimensions — Measurement

Tables

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 11.2.2.

Defined terms used