11.2.2 Stairway construction
Part 11.2 Stairway and ramp construction · NCC 2019: 3.9.1.2
(1) A stairway must be designed to take loading forces in accordance with AS/NZS 1170.1 and must have—
not more than 18 and not less than 2 risers in each flight; and
goings (G), risers (R) and a slope relationship quantity (2R + G) in accordance with Table 11.2.2a, except as permitted by (2) and (3); and
constant goings and risers throughout each flight, except as permitted by (3) and (4), and the dimensions of goings (G) and risers (R) in accordance with (1), (2) and (3) are considered constant if the variation between—
adjacent risers, or between adjacent goings, is not more than 5 mm; and
the largest and smallest riser within a flight, or the largest and smallest going within a flight, is not more than 10 mm; and
risers which do not have any openings that would allow a 125 mm sphere to pass through between the treads; and
treads of solid construction (not mesh or other perforated material) if the stairway is more than 10 m high or connects more than 3 storeys.
(2) In the case of a stairway serving only non-habitable rooms, such as attics, storerooms and the like that are not used on a regular or daily basis—
the going (G), riser (R) and slope relationship quantity (2R + G) in accordance with Table 11.2.2a may be substituted with those in Table 11.2.2b; and
need not comply with (1)(d).
(3) In the case of a stairway with winders —
a maximum of 3 consecutive winders in lieu of a quarter landing in a flight and a maximum of 6 consecutive winders in lieu of a half landing in a flight; and
the going (G) of all winders in lieu of a quarter or half landing may vary from the going of the straight treads within the same flight provided that the going (G) of such winders is constant.
(4) The point of measurement of the going (G) in the slope relationship quantity (2R + G) for tapered treads and treads in spiral stairways as described in Table 11.2.2a (see Figure 11.2.2a, Figure 11.2.2b and Figure 11.2.2c) must be—
for tapered treads, other than treads in a spiral stairway —
not more than 1 m in width, the middle of the unobstructed width of the stairway (see Figure 11.2.2b); and
more than 1 m in width, 400 mm from the unobstructed width of each side of the stairway (see Figure 11.2.2c); and
for treads in spiral stairways, the point seven tenths of the unobstructed width from the face of the centre pole or support towards the handrail side (see Figure 11.2.2d and Figure 11.2.2e).
(5) Riser and going dimensions must be measured in accordance with Figure 11.2.2f.
Table 11.2.2a Riser and going dimensions (mm)
Stair type
Riser (R) (see Figure 11.2.2f)
Going (G) (see Figure 11.2.2f)
Slope relationship (2R+G)
Max
Min
Max
Min
Max
Min
Stairs (other than spiral)
190
115
355
240
700
550
Spiral
220
140
370
210
680
590
Table Notes
Riser and going dimensions must be measured in accordance with Figure 11.2.2f
Table 11.2.2b Riser and going dimensions (mm) — stairways serving non-habitable rooms used infrequently
Riser (R)
Going (G)
Slope relationship (2R+G)
Max
Min
Max
Min
Max
Min
225
130
355
215
700
540
Table Notes
The going (G) must be not more than the tread depth plus a maximum gap of 30 mm between the rear edge of one tread and the nosing of the tread above.
Figure 11.2.2a Measurement of slope relationship — Plan view — Stair with 2 flights
Figure 11.2.2b Measurement of slope relationship — Plan view — Tapered treads not more than 1 m wide
Figure 11.2.2c Measurement of slope relationship — Plan view — Tapered treads more than 1 m wide
Figure 11.2.2d Spiral stairs — Measurement for slope relationship
Figure 11.2.2e Spiral stairs — Measurement of openings in stairs
Figure 11.2.2f Riser and going dimensions — Measurement
Tables
- Table 11.2.2a Riser and going dimensions (mm)
- Table 11.2.2b Riser and going dimensions (mm) — stairways serving non-habitable rooms used infrequently