ABCB Housing Provisions 2025
Part 11.2 Stairway and ramp construction
10 clauses · Open on NCC Online ↗
- 11.2.1 Explanation of termsFigure 11.2.1 depicts stairway members and associated terminology used to describe them in the ABCB Housing Provisions. (2) Some items such as…
- Table 11.2.2a Riser and going dimensions (mm)Stair type | Riser (R) (see Figure 11.2.2f) | Going (G) (see Figure 11.2.2f) | Slope relationship (2R+G) Max | Min | Max | Min | Max | Min Stairs…
- Table 11.2.2b Riser and going dimensions (mm) — stairways serving non-habitable rooms used infrequentlyRiser (R) | Going (G) | Slope relationship (2R+G) Max | Min | Max | Min | Max | Min 225 | 130 | 355 | 215 | 700 | 540 Table Notes The going (G) must…
- 11.2.2 Stairway constructionA stairway must be designed to take loading forces in accordance with AS/NZS 1170.1 and must have— not more than 18 and not less than 2 risers in…
- 11.2.3 RampsAn external ramp serving an external doorway or a ramp within a building must— be designed to take loading forces in accordance with AS/NZS 1170.1;…
- Table 11.2.4 Slip-resistance classificationApplication | Dry surface conditions | Wet surface conditions Ramp not steeper than 1:8 | P4 or R10 | P5 or R12 Tread surface | P3 or R10 | P4 or…
- 11.2.4 Slip resistanceThe requirements for slip-resistance treatment to stair treads, ramps and landings are as set out in (2), (3) and (4). (2) Treads must have— a…
- 11.2.5 LandingsLandings must— be not less than 750 mm long and where this involves a change in direction, the length is measured 500 mm from the inside edge of the…
- 11.2.6 ThresholdsWhere the threshold of a doorway is more than 230 mm above the adjoining surface it must incorporate steps having riser (R) and going (G) dimensions…
- 11.2.7 Fixed platforms, walkways, stairways and ladders for Class 10b structuresA fixed platform, walkway, stairway or ladder and associated landings serving a Class 10b structure must comply with— AS 1657; or for— stairways —…