12.4.5 Installation of free standing heating appliances
Part 12.4 Heating appliances, fireplaces, chimneys and flues · NCC 2019: 3.10.7.5
The installation of a free standing heating appliance must comply with the following:
The appliance must—
be installed with safety clearances determined by testing in accordance with AS/NZS 2918; or
be located not less than 1.2 m from adjoining walls (other than a masonry wall); or
have a heat shield between the adjoining wall (other than a masonry wall) and the heating appliance in accordance with Figure 12.4.5a and Figure 12.4.5b.
Where a heat shield is used, it must be installed in accordance with Figure 12.4.5a and Figure 12.4.5b, and—
have an FRL of not less than 60/60/60; or
be not less than 90 mm thick masonry constructed in accordance with H1D5.
The heating appliance must be installed on a hearth—
complying with 12.4.2(b), except that the hearth must extend 400 mm from the front and sides of the appliance in accordance with Figure 12.4.5a and Figure 12.4.5b; or
where a heat shield is installed, in accordance with Figure 12.4.5a and Figure 12.4.5b.
The flue must—
have been tested and passed the tests required by AS/NZS 2918; and
be installed in accordance with Figure 12.4.5c; and
terminate in accordance with Figure 12.4.3; and
be flashed in accordance with H1D7.
Flue types or installation of flues in areas not specifically covered by Figure 12.4.5a and Figure 12.4.5b and Figure 12.4.5c must be installed in accordance with AS/NZS 2918.
Figure 12.4.5a Acceptable location of free standing heating appliances — Elevation
Figure 12.4.5b Acceptable location of free standing heating appliances — Plan view
Figure 12.4.5c Acceptable flue installation details
Figure Notes
Roof flashing – see H1D7(2).
Hearth – see 12.4.5.
Flue pipe size — 150 mm maximum (for other sizes see AS/NZS 2918).