Housing Provisions clause · ABCB Housing Provisions 2025

13.4.4 External windows and doors

Part 13.4 Building sealing · NCC 2019: 3.12.3.3

Open 13.4.4 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) An external door, internal door between a Class 1 building and an unconditioned Class 10a building, openable window and other such opening must be sealed when serving—

a conditioned space; or

a habitable room in climate zones 4, 5, 6, 7 and 8.

(2) A seal to restrict air infiltration—

for the bottom edge of a door, must be a draft protection device; and

for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compressible strip, fibrous seal or the like.

(3) A window complying with the maximum air infiltration rates specified in AS 2047 need not comply with (2)(b).

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 13.4.4.

State and territory variations all clauses side by side →