Housing Provisions clause · ABCB Housing Provisions 2022
13.4.4 External windows and doors
Part 13.4 Building sealing · NCC 2019: 3.12.3.3
Varied in NT. Check the variation for your state.
(1) An external door, internal door between a Class 1 building and an unconditioned Class 10a building, openable window and other such opening must be sealed when serving—
a conditioned space; or
a habitable room in climate zones 4, 5, 6, 7 and 8.
(2) A seal to restrict air infiltration—
for the bottom edge of a door, must be a draft protection device; and
for the other edges of a door or the edges of an openable window or other such opening, may be a foam or rubber compressible strip, fibrous seal or the like.
(3) A window complying with the maximum air infiltration rates specified in AS 2047 need not comply with (2)(b).
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 13.4.4.