2.2.3 Determination of individual actions
Part 2.2 Structural provisions · NCC 2019: 3.0.3
The magnitude of individual actions must be determined in accordance with the following:
Permanent actions:
the design or known dimensions of the building or structure; and
the unit weight of the construction; and
AS/NZS 1170.1.
Imposed actions:
the known loads that will be imposed during the occupation or use of the building or structure; and
construction activity actions; and
AS/NZS 1170.1.
Wind, snow and earthquake actions:
the applicable annual probability of design event for safety, determined by—
assigning the building or structure an Importance Level in accordance with Table 2.2.3a; and
determining the corresponding annual probability of exceedance for safety in accordance with Table 2.2.3b; and
for wind actions, AS/NZS 1170.2 or AS 4055; and
for snow and ice actions, AS/NZS 1170.3; and
for earthquake actions, AS 1170.4.
Actions not covered in (a), (b) and (c) above:
the nature of the action; and
the nature of the building or structure; and
the Importance Level of the building or structure determined in accordance with Table 2.2.3a; and
AS/NZS 1170.1.
For the purposes of (d) the actions include but are not limited to—
liquid pressure action; and
ground water action; and
rainwater action (including ponding action); and
earth pressure action; and
differential movement; and
time dependent effects (including creep and shrinkage); and
thermal effects; and
ground movement caused by—
swelling, shrinkage or freezing of the subsoil; and
landslip or subsidence; and
siteworks associated with the building or structure; and
construction activity actions.
Table 2.2.3a Importance Levels of buildings and structures
Importance Level
Building types
1
Buildings or structures presenting a low degree of hazard to life and other property in the case of failure.
2
Buildings or structures not included in Importance Level 1.
Table 2.2.3b Design events for safety — annual probability of exceedance
Importance Level
Non-cyclonic wind
Cyclonic wind (wind regions B2 and C)
Cyclonic wind (wind region D)
Snow
Earthquake
1
1:100
1:200
1:250
1:100
1:250
2
1:500
1:500
1:1000
1:150
1:500
Figure 2.2.3 Wind regions
Tables
- Table 2.2.3a Importance Levels of buildings and structures
- Table 2.2.3b Design events for safety — annual probability of exceedance
Changed since NCC 2022. See ABCB Housing Provisions 2022 2.2.3, or show what changed.
The magnitude of individual actions must be determined in accordance … in Importance Level 1. Table 2.2.3b Design events for safety —annual — annual probability of exceedance Importance Level Non-cyclonic wind Cyclonic wind (wind regions B2 and C) Cyclonic wind (wind region D) Snow Earthquake 1 1:100 1:200 1:250 1:100 1:250 2 1:500 1:500 1:1000 1:150 1:500 Figure 2.2.3 Wind regions