3.4.2 Termite management systems
Part 3.4 Termite risk management · NCC 2019: QLD 3.1.4.3, NT 3.1.4.3(d) and (e), 3.1.4.3
Where a termite management system is required it must—
be selected appropriate to Table 3.4.2; and
comply with—
AS 3660.1; or
have been tested and passed the tests required by Section 5 of AS 3660.3; and
have a durable notice installed in accordance with 3.4.3; and
where a chemical termite management system is used, the chemical must be included on the appropriate authority’s pesticides register.
Table 3.4.2 Acceptable termite management systems and components
Building element
Termite management system or component options
Concrete slab-on-ground: slab perimeter or external wall perimeter
Slab edge exposure
Sheet material
Granular material
Chemical
Concrete slab-on-ground: penetrations/control joints/area beneath the slab (see Note)
Sheet material
Granular material
Chemical
Suspended floors
Sheet material
Granular material
Chemical
Attachments to buildings
Termite management system to the attachment
Inspection zone between attachment and building
Table Notes
The entire area beneath the slab must be treated when the slab-on-ground is not designed and constructed in accordance with AS 2870 or AS 3600.
Tables
State and territory variations all clauses side by side →
- NT Replaced Delete clause 3.4.2 and insert NT 3.4.2 as follows: Where a termite management system is required it must— be selected…
- QLD Replaced Delete clause 3.4.2 and insert QLD 3.4.2 as follows: Where a termite management system is required it must— be selected…