Housing Provisions clause · ABCB Housing Provisions 2025

4.2.22 Recessed areas of slabs

Part 4.2 Footings, slabs and associated elements

Open 4.2.22 on NCC Online ↗

(1) Where a recess in a slab is provided, a thickening must be provided in accordance with one of the following:

For recess depths (d) less than or equal to half the nominal slab thickness (see Figure 4.2.22a)—

a thickening must be provided not less than 400 mm measured horizontally from the inside face of each side of the recess (L); and

the reinforcing mesh must—

be bent to accommodate the recess (see Figure 4.2.22a); or

be installed in accordance with (b)(i) and (ii).

For recess depths (d) greater than half the nominal slab thickness (see Figure 4.2.22b)—

top reinforcing mesh must overlap the bottom reinforcing mesh by not less than 400 mm; and

bottom reinforcing mesh must be two layers of SL72.

(2) Concrete cover to reinforcing in (1)(a) and (b) must comply with 4.2.11(5).

(3) Thickening required by (1) must be not less than the sum of recess depth (d) and the required slab depth (D).

(4) Required slab depth (D) must be provided below the recess.

Figure 4.2.22a Recess depths (d) less than or equal to half nominal slab thickness

Figure Notes

L = Extent of thickening required by 4.2.22(1).

D = Slab depth.

d = Recess depth.

Figure 4.2.22b All recess depths (d)

Figure Notes

L = Extent of thickening required by 4.2.22(1).

D = Slab depth.

d = Recess depth.

Changed since NCC 2022. See ABCB Housing Provisions 2022 4.2.22, or show what changed.

(1) Where a recess in a slab is provided, it a thickening must comply be provided in accordance with one of the following: For recess depths (d) less than or equal to half the nominal slab thickness, the reinforcing mesh thickness (see Figure 4.2.22a)— a thickening must have a minimum lap length of be provided not less than 400 mm measured horizontally from the inside face of each side of the recess (L); and the reinforcing mesh must — be bent to accommodate the recess (see Figure 4.2.22a). 4.2.22a); or be installed in accordance with (b)(i) and (ii). For recess depths (d) greater than half the nominal slab thickness (see Figure 4.2.22b)— … to reinforcing in (1)(a) and (b) must comply with 4.2.11(5). (3) Thickening required by (1) must be not less than the sum of recess depth (d) and the required slab depth (D). (4) Required slab depth (D) must be provided below the recess. Figure 4.2.22a Recess depths (d) less than or equal to half nominal slab thickness Figure Notes L = Extent of thickening required by 4.2.22(1). D = Slab depth. d = Recess depth. Figure 4.2.22b Recess All recess depths (d) greater than nominal slab thickness Figure Notes L = Extent of thickening required by 4.2.22(1). D = Slab depth. d = Recess depth.