7.3.3 Flashing
Part 7.3 Roof tiles and shingles · NCC 2019: 3.5.2.3
(1) Flashing for roof tiles must comply with (2) to (7).
(2) Wall and step flashings:
For masonry or similar walls, flashing must—
follow the roof line, allowing not less than 75 mm upturn to the wall and a minimum of 150 mm in width and moulded into the tiles; and
have a horizontal overflashing, stepped overflashing or raked overflashing built into the masonry leaf or veneer, except that one continuous flashing may be used as both an apron flashing or an overflashing; and
have joints overlap the one below by not less than 75 mm in the direction of flow.
For flashing where the upturn can be fixed to or behind the supporting frame or cladding, it must—
follow the roof line, allowing not less than 75 mm upturn to the wall and a minimum of 150 mm in width and moulded into the tiles; and
be fastened into or behind the wall cladding at each end and at a maximum of 600 mm centres; and
have joints overlap the one below by not less than 75 mm in the direction of flow.
(3) Flashing of penetrations must—
be either collar, apron or other purpose made flashings; and
have a minimum upturn on the penetration of not less than 75 mm and a minimum of 150 mm in width surrounding the penetration and be moulded into the tiles; and
permit the total drainage of the area above the penetration.
(4) Joints in flashing must be not less than 75 mm and lapped in the direction of fall of the roof.
(5) Fixings for flashings must be compatible with the flashing material.
(6) Lead flashings must not be used on any roof that is part of a drinking water catchment area.
(7) Acceptable flashing configurations, including typical details for standard, and bedded and pointed valleys, are shown in Figures 7.3.3a, 7.3.3b, 7.3.3c, 7.3.3d, 7.3.3e, 7.3.3f and 7.3.3g.
Figure 7.3.3a Flashing abutting a masonry wall
Figure 7.3.3b Flashing abutting a weatherboard wall or similar cladding
Figure 7.3.3c Stepped flashing to a masonry wall
Figure 7.3.3d Pipe penetration flashing
Figure 7.3.3e Chimney flashing
Figure 7.3.3f Standard valley
Figure 7.3.3g Bedded and pointed valley for high rainfall areas (refer definition of low rainfall intensity area)