Housing Provisions clause · ABCB Housing Provisions 2025

7.3.5 Anti-ponding device/board

Part 7.3 Roof tiles and shingles · NCC 2019: 3.5.2.5

Open 7.3.5 on NCC Online ↗

(1) An anti-ponding device/board must be provided where sarking is installed on—

roofs with a pitch less than 20°; and

roofs with no eaves overhang, regardless of the roof pitch.

(2) An anti-ponding device required by (1) must be water resistant and fixed along the eaves line from the top of the fascia back up the rafter with a clearance of approximately 50 mm below the first batten (See Figure 7.3.5).

Figure 7.3.5 Typical installation of anti-ponding device/board

Figure Notes

Sarking is required by 7.3.4.

Anti-ponding device is required by 7.3.5.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 7.3.5.

Clauses referred to