Housing Provisions clause · ABCB Housing Provisions 2025

7.3.4 Sarking

Part 7.3 Roof tiles and shingles · NCC 2019: 3.5.2.4

Open 7.3.4 on NCC Online ↗

Sarking must—

be provided in accordance with Table 7.3.4; and

comply with AS 4200.1 and be installed with—

each adjoining sheet or roll being—

overlapped not less than 150 mm; or

taped together; and

sarking fixed to supporting members at not more than 300 mm centres; and

no sags more than 40 mm in the sarking.

Table 7.3.4 Sarking requirements for tiled roofs

Roof pitch

Maximum rafter/truss top chord length without sarking (mm) Note 1

<18°

N/A Note 2

≥18° <20°

4 500

≥20° <22°

5 500

≥22°

6 000

Table Notes

The maximum rafter/truss top chord length is measured from the topmost point of the rafter/truss i.e. the apex downwards. Where the maximum length is exceeded, sarking must be installed over the remainder of the rafter/truss top chord length towards the eave line of the roof, or equivalent where the building has no eaves.

All tiled roofs with a pitch less than 18 degrees must be provided with sarking, regardless of rafter/truss chord length.

Tables

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 7.3.4.

Defined terms used