7.5.6 Flashings to wall openings
Part 7.5 Timber and composite wall cladding · NCC 2019: 3.5.4.6
Openings in external wall cladding exposed to the weather must be flashed with materials complying with AS/NZS 2904 and in accordance with the following:
Flashings must be provided to bottom, tops and sides of openings, except as permitted by (d), and must be installed so that the flashing —
extends not less than 110 mm beyond the reveals on each side of the opening where practicable; and
is attached to the window and wall framing; and
at the top and bottom of the opening, drains to the outside face of the wall or cladding.
Joins in the flashing must—
overlap by not less than 75 mm in the direction of flow; and
be securely fastened at intervals of not more than 40 mm; and
have sealant installed between laps.
The method of flashing must be suitable for the framing and cladding used and any reveal for the window or door system or any architrave or finishing trims that may be installed.
The top of an opening need not be flashed where it is adequately protected by an eave of a width more than 3 times the height of the cladding above the opening (See Figure 7.5.6).
Flashings must be securely fixed at least 25 mm under the cladding and extend over the ends and edges of the framing of the opening.
Figure 7.5.6 Weather protection of openings