Housing Provisions clause · ABCB Housing Provisions 2025

8.4.4 Full height framed glazed panels

Part 8.4 Glazing human impact · NCC 2019: 3.6.4.3

Open 8.4.4 on NCC Online ↗

(1) A glazed panel located in a building so that it is capable of being mistaken for an unobstructed opening must be glazed with Grade A safety glazing material in accordance with Table 8.4.2.

(2) Glazed panels are not considered an unobstructed opening where any of the following apply:

The clear opening width is not more than 500 mm.

The lowest sight line of the opening is not less than 500 mm above the highest abutting finished floor level.

The glass is made apparent by means of transoms, colonial bars, other components of the glazing system, permanent motifs or other decorative treatment on or etched into the glass, of sufficient magnitude to be readily apparent, or the glass is opaquely coloured or patterned to indicate its presence.

A chair rail or handrail not less than 40 mm thick, or the like, is provided at a height of not less than 700 mm above the adjoining ground level.

The difference in floor level on either side of the panel is greater than 1000 mm.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 8.4.4.