9.2.1 External walls of Class 1 buildings

Part 9.2 Fire separation of external walls · NCC 2019: SA 3.7.2.2(b) and (c), 3.7.2.2

Open 9.2.1 on NCC Online ↗
Varied in SA. Check the variation for your state.

An external wall of a Class 1 building, and any openings in that wall, must comply with 9.2.3 if the wall is less than—

900 mm from an allotment boundary other than the boundary adjoining a road alignment or other public space; or

1.8 m from another building on the same allotment other than a Class 10 building associated with the Class 1 building or a detached part of the same Class 1 building.

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 9.2.1.