South Australia variation · ABCB Housing Provisions 2025
SA 9.2.1 External walls of Class 1 buildings
SA Part 9.2 Fire separation of external walls · varies 9.2.1 External walls of Class 1 buildings
Delete clause 9.2.1 and insert SA 9.2.1 as follows:
An external wall of a Class 1 building, and any openings in that wall, must comply with 9.2.3 if the wall is less than—
900 mm from an allotment boundary other than the boundary adjoining a road alignment or other public space; or
1.8 m from another building on the same allotment other than an appurtenant Class 10 building associated with the Class 1 building or a detached part of the same Class 1 building; or
3 m from a brush fence.
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 SA 9.2.1.