9.2.5 Protection of Class 1 buildings — Class 10a between Class 1 and the allotment boundary
Part 9.2 Fire separation of external walls · NCC 2019: Figure 3.7.2.4
The following methods are acceptable for the protection of a Class 1 building where a Class 10a building is located between or adjacent to a Class 1 building and a boundary alignment that is not a boundary with a road alignment or other public space:
The Class 10a building is not less than 900 mm from the allotment boundary, other than the boundary adjoining a road alignment or other public space, as shown in Figure 9.2.5a.
An external wall of the Class 10a building which is less than 900 mm from an allotment boundary, other than the boundary adjoining a road alignment or other public space, complies with 9.2.3 as shown in Figure 9.2.5b.
An external wall of the Class 10a building, which is less than 900 mm from the Class 1 building, complies with 9.2.3 as shown in Figure 9.2.5c.
The Class 1 building is not less than 900 mm from the Class 10a building, as shown in Figure 9.2.5d.
An external wall of the Class 1 building, which is less than 900 mm from the Class 10a building, complies with 9.2.3, as shown in Figure 9.2.5e.
An external wall of the Class 10a building which is less than 900 mm from an allotment boundary other than the boundary adjoining a road alignment or other public space, complies with 9.2.3, as shown in Figure 9.2.5f.
An external wall of the Class 10a building, which is less than 900 mm from the external wall of the Class 1 building, complies with 9.2.3, as shown in Figure 9.2.5g.
An external wall of the Class 1 building, which is less than 900 mm from a Class 10a building that is situated less than 900 mm from an allotment boundary, complies with 9.2.3, as shown in Figure 9.2.5h.
The external wall of the Class 1 and Class 10a building which are less than 900 mm from an allotment boundary, other than the boundary adjoining a road alignment or other public space, complies with 9.2.3 as shown in Figure 9.2.5i.
Figure 9.2.5a Class 10a building 900 mm from allotment boundary
Figure 9.2.5b External wall to Class 10a building with FRL (method 1)
Figure 9.2.5c External wall to Class 10a building with FRL (method 2)
Figure 9.2.5d 900 mm separation between buildings
Figure 9.2.5e Class 1 building with FRL to external wall
Figure 9.2.5f External wall of adjacent Class 10a building with FRL (method 1)
Figure 9.2.5g External wall of adjacent Class 10a building with FRL (method 2)
Figure 9.2.5h Class 1 building with FRL to external wall
Figure 9.2.5i External wall to Class 10 building with FRL