9.2.6 Protection of Class 1 buildings — Class 10a between Class 1 and other buildings on allotment
Part 9.2 Fire separation of external walls · NCC 2019: Figure 3.7.2.5
The following methods are acceptable for the protection of a Class 1 building where a Class 10a building is located between or adjacent to a Class 1 building it is associated with and another building on the same allotment:
The Class 10a building is not less than 1.8 m from the other building, as shown in Figure 9.2.6a.
An external wall of the Class 10a building, which is less than 1.8 m from the other building, complies with 9.2.3, as shown in Figure 9.2.6b.
An e xternal wall of the Class 10a building, which is less than 1.8 m from the Class 1 building, complies with 9.2.3, as shown in Figure 9.2.6c.
The Class 1 building is not less than 1.8 m from the Class 10a building, as shown in Figure 9.2.6d.
An external wall of the Class 1 building, which is less than 1.8 m from the Class 10a building, complies with 9.2.3, as shown in Figure 9.2.6e.
An external wall of the Class 10a building, which is less than 1.8 m from the external wall of the other building, complies with 9.2.3, as shown in Figure 9.2.6f.
An external wall of the Class 10a building, which is less than 1.8 m from the external wall of the Class 1 building, complies with 9.2.3, as shown in Figure 9.2.6g.
An external wall of the Class 1 and 10a building, which is less than 1.8 m from the external wall of the other building, complies with 9.2.3, as shown in Figure 9.2.6h.
Figure 9.2.6a Class 10a building 1.8 m from other building on allotment
Figure 9.2.6b External wall to Class 10a building with FRL (method 1)
Figure 9.2.6c External wall to Class 10a building with FRL (method 2)
Figure 9.2.6d 1.8 m separation between Class 1 and 10a
Figure 9.2.6e Class 1 building with FRL to external wall
Figure 9.2.6f External wall of adjacent Class 10a building with FRL (method 1)
Figure 9.2.6g External wall of adjacent Class 10a building with FRL (method 2)
Figure 9.2.6h Class 1 and 10 building with FRL to external wall