Housing Provisions clause · ABCB Housing Provisions 2025
9.3.3 Roof lights
Part 9.3 Fire protection of separating walls and floors · NCC 2019: 3.7.3.4
Combustible roof lights, skylights or the like installed in a roof or part of a roof required to have a non-combustible covering must—
have an aggregate area not more than 20% of the roof or part of the roof; and
be not less than 900 mm from the vertical projection of a separating wall extending to the underside of the roof covering.
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 9.3.3.