NSW 9.4.2 Construction of floors
NSW Part 9.4 Fire protection of garage top dwellings · varies 9.4.2 Separating floors
Insert NSW clause 9.4.2 in clause 9.4.2 as follows:
(1) A floor required by NSW 9.4.1(1) or NSW 9.4.1(3)(b) must—
have an FRL of not less than 30/30/30 when tested from the underside; or
have a fire-protective covering on the underside of the floor, including beams incorporated in it; or
be a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes.
(2) Where a floor subject to (1)(a) depends on direct vertical or lateral support from another part to maintain its FRL, that supporting part must have an FRL of not less than 30/-/-.
(3) Where a service passes through a floor referred to in (1), the penetration must not reduce the performance of the floor or covering.