9.4.1 Walls requiring protection
Part 9.4 Fire protection of garage top dwellings · NCC 2019: NSW 1.1.1, 3.7.4.2
(1) Where parts of a Class 1a dwelling are located above a Class 10a private garage that is not associated with the Class 1a dwelling—
any wall separating parts of the Class 1a dwelling from the private garage not associated with the dwelling must comply with (2); and
any private garage associated with and located below the Class 1a dwelling must be separated from the private garage not associated with the dwelling by a wall complying with (2).
(2) A wall required by (1) must—
have either—
an FRL of not less than 60/60/60 when tested from the private garage associated with another dwelling side; or
be of masonry construction not less than 90 mm thick; and
commence at the footings or ground slab; and
extend to the underside of a separating floor complying with 9.4.2; and