Northern Territory variation · ABCB Housing Provisions 2025

NT 13.5.3 Ventilation openings

NT Part 13.5 Ceiling fans

Open on NCC Online ↗

Insert NT clause 13.5.3 in clause 13.5.3 as follows:

(1) The total ventilation opening area required by Table NT 13.5.2 to a habitable room must—

be connected by a breeze path complying with (b) to another ventilation opening in another room or space; or

be provided by a minimum of two ventilation openings located within the same habitable room, with each ventilation opening having an area of not less than 25% of the area required by Table NT 13.5.2.

(2) A breeze path required by (1)(a) must—

pass through not more than two openings in the internal walls with each opening having an area of not less than 1.5 m2; and

have a distance along the breeze path between ventilation opening of not more than 20 m.

Changed since NCC 2022. See ABCB Housing Provisions 2022 NT 13.5.3, or show what changed.