Part 8.3 Glass
6 clauses · Open on NCC Online ↗
- 8.3.1 ApplicationGlazing must comply with the following: 8.3.2 for glass sizes and installation. 8.3.3 for fully framed glazing installed in the perimeter of…
- 8.3.2 Glazing sizes and installationGlazing used in buildings must comply with the following: Glazing used in the perimeter of buildings and supported on all sides must comply with the…
- Table 8.3.3a Glass thickness for wind class not exceeding N1: monolithic annealed glass (mm)Edge (mm) | 300 | 450 | 600 | 750 | 900 | 1050 | 1200 | 1350 | 1500 | 1650 300 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 450 | 3 | 3 | 3 | 3 | 3 | 3 |…
- Table 8.3.3b Glass thickness for wind class not exceeding N2: monolithic annealed glass (mm)Edge (mm) | 300 | 450 | 600 | 750 | 900 | 1050 | 1200 | 1350 | 1500 | 1650 300 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 450 | 3 | 3 | 3 | 3 | 3 | 3 |…
- Table 8.3.3c Glass thickness for wind class not exceeding N3: monolithic annealed glass (mm)Edge (mm) | 300 | 450 | 600 | 750 | 900 | 1050 | 1200 | 1350 | 1500 | 1650 300 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 450 | 3 | 3 | 3 | 3 | 3 | 3 |…
- 8.3.3 Fully framed glazing installed in perimeter of buildingsFully framed (supported on all sides) monolithic annealed glass installed in the perimeter of buildings must comply with— if the building is located…