SA 10.2.1 Wet areas
SA Part 10.2 Wet area waterproofing · varies 10.2.1 Wet areas
Delete clause 10.2.1 and insert SA 10.2.1 as follows:
Building elements in wet areas within a building must—
be waterproof or water resistant in accordance with 10.2.2 to 10.2.6, except that—
in any room containing a washing machine, the wall area from finished floor level to a minimum of 75 mm above and 75 mm each side of the washing machine tap outlets must be water resistant; and
where a vessel is inset into a bench top in a kitchen, bar area, kitchenette or domestic food and beverage preparation area—
wall junctions and joints within 150 mm above the vessel must be water resistant for the extent of the vessel; and
the perimeter edges of the vessel must be water resistant for the extent of the vessel (see SA Figures 10.2.1a, 10.2.1b and 10.2.1c); and
penetrations in horizontal surfaces for tap and spout outlets in kitchens, bar areas, kitchenettes or domestic food and beverage preparation areas, must be waterproof; and
have the wet area construction practices in accordance with
AS 3740; and
have floor wastes provided in accordance with SA 10.2.33; and
where floor wastes are provided for drainage of floors in bathrooms and laundries, the floors, floor/wall junction and penetration must be waterproof.
Insert SA figure (10.2.1a) 10.2.1 as follows:
SA Figure 10.2.1a: Typical water resistant junctions and joints for bench tops with inset vessels and vessels abutting walls
Insert SA figure (10.2.1b) 10.2.1 as follows:
SA Figure 10.2.1b: Typical water resistant junctions and joints for bench tops with inset vessels and vessels abutting walls
Insert SA figure (10.2.1c) 10.2.1 as follows:
SA Figure 10.2.1c: Typical water resistant junctions and joints for bench tops with inset vessels and vessels abutting walls
Changed since NCC 2022. See ABCB Housing Provisions 2022 SA 10.2.1, or show what changed.
Delete clause 10.2.1 and insert SA 10.2.1 as follows: Building … domestic food and beverage preparation areas, must be waterproof; and comply have the wet area construction practices in accordance with clauses 10.2.7 to 10.2.32; or AS 3740; and have floor wastes provided in accordance with … for bench tops with inset vessels and vessels abutting walls