South Australia variation · ABCB Housing Provisions 2025

SA 9.2.8 Open carports

SA Part 9.2 Fire separation of external walls · varies 9.2.8 Open carports

Open on NCC Online ↗

Delete clause 9.2.8 and insert SA 9.2.8 as follows:

A Class 10a carport or verandah is exempt from complying with 9.2.4(1) if—

it has—

two or more sides open and not less than one third of its perimeter open and, for the purpose of this clause, a side is considered to be open if the roof covering adjacent to that side is not less than 500 mm from another building on the same allotment or allotment boundary; or

any part of the external wall of the Class 1 building located less than 2 m from the allotment boundary or less than 4 m from another Class 1 building on the same allotment is fire-resisting to the underside of a non-combustible roof covering or to the underside of a non-combustible ceiling lining (see SA Figure 9.2.8a, SA Figure 9.2.8b and SA Figure 9.2.8c); and

it has polycarbonate or non-combustible roof covering and any ceiling lining and wall cladding, including gables, is also non-combustible (see Figure 9.2.8a); and

it does not provide direct vertical support to any part of the Class 1 building; and

in the case where it has a common roof structure with the Class 1 building and the carport or verandah does not have a ceiling (see Figure 9.2.8b), the opening between the top of the wall of the Class 1 building and the underside of the roof covering is infilled with—

non-combustible material; or

construction with non-combustible material on the carport or verandah side; and

in the case where two carports or verandahs have a common roof structure with two different Class 1 buildings and the carports or verandahs have a ceiling, the roof space or ceiling space between the top of the ceiling and the underside of the roof covering is infilled as follows—

vertically between the two Class 1 buildings and between the two appurtenant carports of verandahs in accordance with (d) (see SA Figure 9.2.8d); or

vertically between the two Class 1 buildings and between the two appurtenant carports or verandahs in accordance with (d), except that the construction must be clad with non-combustible materials on both sides and must not be crossed by timber or other combustible building elements except for roof battens with dimensions of 75 × 50 mm or less, roof sarking-type material or a timber gutter board not less than 20 mm thick.

Insert SA figure (9.2.8a) 9.2.8 as follows:

SA Figure 9.2.8a: Fire-resisting requirements for carports or verandahs without a ceiling

Insert SA figure (9.2.8b) 9.2.8 as follows:

SA Figure 9.2.8b: Fire-resisting requirements for carports or verandahs with a non-combustible ceiling

Insert SA figure (9.2.8c) 9.2.8 as follows:

SA Figure 9.2.8c: Fire-resisting requirements for external walls in carports and verandahs that share a common roof space

Insert SA figure (9.2.8d) 9.2.8 as follows:

SA Figure 9.2.8d: Fire-resisting requirements for roof space openings in carports and verandahs with a ceiling that share a common roof space

Changed since NCC 2022. See ABCB Housing Provisions 2022 SA 9.2.8, or show what changed.

Delete clause 9.2.8 and insert SA 9.2.8 as follows: A Class 10a carport or verandah is exempt from complying with 9.2.4(1) if — it has … side is not less than 500 mm from another building on the same allotment or allotment boundary; or any part of the external wall … verandahs with a ceiling that share a common roof space

Removed words are struck through; added words are highlighted. Comparison of the text only.

The national clause