9.2.8 Open carports
Part 9.2 Fire separation of external walls · NCC 2019: SA 3.7.2.6(a), 3.7.2.6
A Class 10a carport is exempt from complying with 9.2.4(1) if—
it has two or more sides open and not less than one third of its perimeter open; and
for the purposes of (a), a side is considered to be open if the roof covering adjacent to that side is not less than 500 mm from another building on the same allotment or allotment boundary; and
it has a polycarbonate or non-combustible roof covering; and
any ceiling lining and wall cladding, including gables, is non-combustible (see Figure 9.2.8a); and
it does not provide direct vertical support to any part of the Class 1 building; and
in the case where it has a common roof structure with the Class 1 building and the carport does not have a ceiling (See Figure 9.2.8b), the opening between the top of the wall of the Class 1 building and the underside of the roof covering is infilled with—
a non-combustible material; or
construction clad with non-combustible material on the carport side.
Figure 9.2.8a Identifying an open carport
Figure 9.2.8b Requirements for non-combustible infill panels to carport
Changed since NCC 2022. See ABCB Housing Provisions 2022 9.2.8, or show what changed.