Table · ABCB Housing Provisions 2025
Table 13.2.3b Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 1 – two (or more) storey dwelling
| Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA≤ 0.23 | 0.23< SA≤0.32 | 0.32< SA≤0.42 | 0.42< SA≤0.53 | 0.53< SA≤0.64 |
|---|---|---|---|---|---|---|---|
| Vented | Yes | < 1.0 | 1.5 | 1.5 | 1.5 | 1.5 | 2.0 |
| ≥ 1.0 to < 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | ||
| ≥ 1.5 to < 2.0 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | ||
| ≥ 2.0 | 1.5 | 1.5 | 1.5 | 2.0 | 2.0 | ||
| No | < 1.0 | 2.0 | 2.5 | 4.0 | 5.0 | X | |
| ≥ 1.0 to < 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 2.5 | ||
| ≥ 1.5 to < 2.0 | 1.5 | 1.5 | 1.5 | 2.0 | 2.0 | ||
| ≥ 2.0 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | ||
| Standard | Yes | < 1.0 | 1.5 | 1.5 | 2.0 | 3.0 | 4.0 |
| ≥ 1.0 to < 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 2.5 | ||
| ≥ 1.5 to < 2.0 | 1.5 | 1.5 | 1.5 | 1.5 | 2.0 | ||
| ≥ 2.0 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | ||
| No | < 1.0 | 2.5 | 4.0 | 6.0 | X | X | |
| ≥ 1.0 to < 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 4.0 | ||
| ≥ 1.5 to < 2.0 | 1.5 | 1.5 | 2.0 | 2.0 | 2.5 | ||
| ≥ 2.0 | 1.5 | 1.5 | 1.5 | 2.0 | 2.5 |
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
X = not permitted.
Table for 13.2.3 Roofs and ceilings
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.3b.