Table 13.2.3c Pitched roof with horizontal ceiling – minimum R-Value for ceiling insulation: climate zone 2

Part 13.2 Building fabric

Open Table 13.2.3c on NCC Online ↗
Roof ventilationReflective insulation under-roofUnder-roof insulation R-ValueSA ≤ 0.230.23 < SA ≤ 0.320.32 < SA ≤ 0.420.42 < SA ≤ 0.64
VentedYesAny2.5
No< 0.52.53.03.03.5
≥ 0.52.5
StandardYesAny2.5
No< 0.53.03.03.54.0
≥ 0.5 to < 1.02.52.52.53.0
≥ 1.02.5

Table Notes

SA = solar absorptance.

A roof is considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area, with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area, with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.3c.