Table · ABCB Housing Provisions 2025
Table 13.2.3t Metal-framed flat, skillion or cathedral roof – minimum Total R-Value to account for thermal bridging
| Minimum ceiling insulation R-Value from Tables 13.2.3j to 13.2.3r | Minimum Total R-Value to account for thermal bridging – heat flow down | Minimum Total R-Value to account for thermal bridging – heat flow up |
|---|---|---|
| 1.0 | 1.40 | 1.32 |
| 1.5 | 1.86 | 1.78 |
| 2.0 | 2.29 | 2.21 |
| 2.5 | 2.71 | 2.63 |
| 3.0 | 3.11 | 3.02 |
| 3.5 | 3.31 | 3.22 |
| 4.0 | 3.66 | 3.57 |
| 4.5 | 3.98 | 3.90 |
| 5.0 | 4.32 | 4.22 |
| 5.5 | 4.63 | 4.53 |
| 6.0 | 4.93 | 4.82 |
Table Notes
Minimum Total R-Values are in-situ values. They account for compression of insulation.
Direction of heat flow must be determined in accordance with Table 13.2.3v.
Table for 13.2.3 Roofs and ceilings
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.3t.