Table 13.2.3s Metal-framed pitched roof with horizontal ceiling – minimum Total R-Value of ceiling to account for thermal bridging

Part 13.2 Building fabric

Open Table 13.2.3s on NCC Online ↗
Minimum ceiling insulation R-Value from Tables 13.2.3a to 13.2.3i as applicableMinimum ceiling Total R-Value
1.51.38
2.01.74
2.52.09
3.02.43
3.52.63
4.02.95
4.53.27
5.03.59
5.53.91
6.04.23

Table Notes

The Total R-Value calculation only includes the ceiling frame, insulation and ceiling lining. It is not to include internal air films, roof space or roof lining.

Minimum ceiling Total R-Values are in-situ values. They account for compression of insulation.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.3s.