Table · ABCB Housing Provisions 2025

Table 13.2.3x Total R-Value for roofs constructed with insulated sandwich panels

Part 13.2 Building fabric

Open Table 13.2.3x on NCC Online ↗
Climate zoneSA ≤ 0.230.23 < SA ≤ 0.320.32 < SA ≤ 0.420.42 < SA ≤ 0.530.53 < SA ≤ 0.640.64 < SA ≤ 0.730.73 < SA ≤ 0.850.85 < SA ≤ 0.96
1 (single storey dwelling)1.403.31XXXXXX
1 (two or more storey dwelling)1.863.314.32XXXXX
2 (heat flow down)3.113.113.313.663.66XXX
2 (heat flow up)3.023.023.223.573.57XXX
3 (heat flow down)3.313.664.32XXXXX
3 (heat flow up)3.223.574.22XXXXX
43.223.223.223.223.22XXX
53.023.023.023.023.02XXX
63.573.573.573.573.573.573.573.57
74.223.903.903.573.573.223.223.22
83.903.573.573.223.223.023.023.02

Table Notes

SA = solar absorptance.

Direction of heat flow must be determined in accordance with Table 13.2.3v.

X = not permitted.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.3x.