Table · ABCB Housing Provisions 2022
Table 13.2.3x Total R-Value for roofs constructed with insulated sandwich panels
| Climate zone | SA ≤ 0.23 | 0.23 < SA ≤ 0.32 | 0.32 < SA ≤ 0.42 | 0.42 < SA ≤ 0.53 | 0.53 < SA ≤ 0.64 | 0.64 < SA ≤ 0.73 | 0.73 < SA ≤ 0.85 | 0.85 < SA ≤ 0.96 |
|---|---|---|---|---|---|---|---|---|
| 1 (single storey dwelling) | 1.40 | 3.31 | X | X | X | X | X | X |
| 1 (two or more storey dwelling) | 1.86 | 3.31 | 4.32 | X | X | X | X | X |
| 2 (heat flow down) | 3.11 | 3.11 | 3.31 | 3.66 | 3.66 | X | X | X |
| 2 (heat flow up) | 3.02 | 3.02 | 3.22 | 3.57 | 3.57 | X | X | X |
| 3 (heat flow down) | 3.31 | 3.66 | 4.32 | X | X | X | X | X |
| 3 (heat flow up) | 3.22 | 3.57 | 4.22 | X | X | X | X | X |
| 4 | 3.22 | 3.22 | 3.22 | 3.22 | 3.22 | X | X | X |
| 5 | 3.02 | 3.02 | 3.02 | 3.02 | 3.02 | X | X | X |
| 6 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 | 3.57 |
| 7 | 4.22 | 3.90 | 3.90 | 3.57 | 3.57 | 3.22 | 3.22 | 3.22 |
| 8 | 3.90 | 3.57 | 3.57 | 3.22 | 3.22 | 3.02 | 3.02 | 3.02 |
Table Notes
SA = solar absorptance.
Direction of heat flow must be determined in accordance with Table 13.2.3v.
X = not permitted.
Table for 13.2.3 Roofs and ceilings
Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.3x.