Table · ABCB Housing Provisions 2025

Table 13.2.5d Masonry cavity wall – minimum insulation R-Value: climate zone 2

Part 13.2 Building fabric

Open Table 13.2.5d on NCC Online ↗
SAOverhang (mm)Wall height (m)
≤ 2.4> 2.4 to ≤ 2.7> 2.7 to ≤ 3.0> 3.0 to ≤ 3.6
≤ 0.3500.250.250.250.51
> 0 to ≤ 3000.00.250.250.51
> 300 to ≤ 4500.00.00.250.51
> 450 to ≤ 6000.00.00.250.51
> 600 to ≤ 9000.00.00.250.25
> 900 to ≤ 12000.00.250.250.25
> 1200 to ≤ 15000.00.250.250.25
> 15000.00.250.250.25
> 0.35 to ≤ 0.500.250.250.250.51
> 0 to ≤ 3000.00.250.250.51
> 300 to ≤ 4500.00.00.250.51
> 450 to ≤ 6000.00.00.250.51
> 600 to ≤ 9000.00.00.250.25
> 900 to ≤ 12000.00.00.00.25
> 1200 to ≤ 15000.250.00.250.25
> 15000.250.250.250.25
> 0.5 to ≤ 0.700.250.250.510.51
> 0 to ≤ 3000.00.250.250.51
> 300 to ≤ 4500.00.00.250.51
> 450 to ≤ 6000.00.00.250.51
> 600 to ≤ 9000.00.00.250.25
> 900 to ≤ 12000.00.00.00.25
> 1200 to ≤ 15000.00.00.00.25
> 15000.00.00.250.25

Table Notes

SA = solar absorptance.

R-Values listed are for the labelled, declared R-Value of insulation.

This Table shows wall heights for single storey dwellings. For two-storey (or more) dwellings, add R0.25 to the R-Values given in this Table.

Table for 13.2.5 External walls

Changed since NCC 2022. See ABCB Housing Provisions 2022 Table 13.2.5d, or show what changed.

SA | Overhang (mm) | Wall height (m) ≤ 2.4 … | 0.0 | 0.25 | 0.25 | 0.25 > 1500 to ≤ 1800 | 0.0 | 0.25 | 0.25 | 0.25 > 0.35 … | 0.25 | 0.0 | 0.25 | 0.25 > 1500 to ≤ 1800 | 0.25 | 0.25 | 0.25 | 0.25 > 0.5 … | 0.0 | 0.0 | 0.0 | 0.25 > 1500 to ≤ 1800 | 0.0 | 0.0 | 0.25 | 0.25 Table Notes … dwellings, add R0.25 to the R-Values given in this Table.

Removed words are struck through; added words are highlighted. Comparison of the text only.