13.2.5 External walls

Part 13.2 Building fabric · NCC 2019: NSW 3.12.1.1, 3.12.1.4

Open 13.2.5 on NCC Online ↗
Varied in NT. Check the variation for your state.

(1) Except for the external wall of a sub-floor space below a suspended floor and lightweight wall construction, wall insulation must have a minimum R-Value —

in climate zone 1, in accordance with Table 13.2.5a; and

in climate zone 2, in accordance with Tables 13.2.5c and 13.2.5d as applicable; and

in climate zone 3, in accordance with Table 13.2.5e; and

in climate zone 4, in accordance with Tables 13.2.5g and 13.2.5h as applicable; and

in climate zone 5, in accordance with Tables 13.2.5i and 13.2.5j as applicable; and

in climate zone 6, in accordance with Tables 13.2.5k and 13.2.5l as applicable; and

In climate zone 7, in accordance with Tables 13.2.5m and 13.2.5n as applicable.

(2) For lightweight wall construction, wall insulation must have a minimum R-Value —

in climate zone 1, in accordance with Table 13.2.5b; and

in climate zone 2, in accordance with Table 13.2.5c, with R0.3 added; and

in climate zone 3, in accordance with Table 13.2.5f; and

in climate zone 4, in accordance with Table 13.2.5g, with R0.3 added; and

in climate zone 5, in accordance with Table 13.2.5i, with R0.3 added; and

in climate zone 6, in accordance with Table 13.2.5k, with R0.3 added; and

in climate zone 7, in accordance with Table 13.2.5m, with R0.3 added; and

in climate zone 8, in accordance with Table 13.2.5o.

(3) In climate zones 1 to 5, the solar absorptance of the outer surface of a wall used in (1) or (2) must be not more than 0.7.

(4) The thermal bridging in a metal-framed wall must be addressed by—

achieving the Total R-Value in Tables 13.2.5p, 13.2.5q and 13.2.5r, calculated in accordance with AS/NZS 4859.2; or

complying with one of the options in Tables 13.2.5s, 13.2.5t and 13.2.5u.

(5) A metal-framed wall that forms part of the building envelope must have a thermal break, consisting of a material with an R-Value of not less than R0.2, installed at all points of contact between the external cladding and the metal frame if the wall—

does not have a wall lining or has a wall lining that is fixed directly to the metal frame; and

is clad with weatherboards, fibre-cement or the like, or metal sheeting fixed to the metal frame.

(6) The requirements of (5) do not apply to walls constructed using insulated sandwich panels.

Table 13.2.5a Concrete block walls – minimum insulation R-Value: climate zone 1

SA

Overhang (mm)

Wall height (m)

≤ 2.4

> 2.4 to ≤ 2.7

> 2.7 to ≤ 3.0

> 3.0 to ≤ 3.6

≤ 0.3

0

X

X

X

X

> 0 to ≤ 300

Reflective

X

X

X

> 300 to ≤ 450

0.0

Reflective

1.5

X

> 450 to ≤ 600

0.0

Reflective

1.0

X

> 600 to ≤ 900

0.0

0.0

Reflective

2.0

> 900 to ≤ 1200

0.0

0.0

Reflective

1.0

> 1200 to ≤ 1500

0.0

0.0

0.0

Reflective

> 1500 to ≤ 1800

0.0

0.0

0.0

Reflective

> 1800

0.0

0.0

0.0

Reflective

> 0.3 to ≤ 0.4

0

X

X

X

X

> 0 to ≤ 300

1.0

X

X

X

> 300 to ≤ 450

1.0

1.0

X

X

> 450 to ≤ 600

Reflective

Reflective

2.0

X

> 600 to ≤ 900

0.0

Reflective

Reflective

X

> 900 to ≤ 1200

0.0

0.0

Reflective

1.5

> 1200 to ≤ 1500

0.0

0.0

Reflective

Reflective

> 1500 to ≤ 1800

0.0

0.0

0.0

Reflective

> 1800

0.0

0.0

0.0

Reflective

> 0.4 to ≤ 0.5

0

X

X

X

X

> 0 ≤ 300

1.0

X

X

X

> 300 to ≤ 450

1.0

1.5

X

X

> 450 to ≤ 600

Reflective

1.0

X

X

> 600 to ≤ 900

0.0

Reflective

1.0

X

> 900 to ≤ 1200

0.0

Reflective

Reflective

2.0

> 1200 to ≤ 1500

0.0

0.0

Reflective

1.0

> 1500 to ≤ 1800

0.0

0.0

Reflective

Reflective

> 1800

0.0

0.0

0.0

Reflective

> 0.5 to ≤ 0.6

0

X

X

X

X

> 0 to ≤ 300

1.5

X

X

X

> 300 to ≤ 450

1.0

X

X

X

> 450 to ≤ 600

Reflective

1.5

X

X

> 600 to ≤ 900

Reflective

Reflective

1.5

X

> 900 to ≤ 1200

0.0

Reflective

Reflective

X

> 1200 to ≤ 1500

0.0

Reflective

Reflective

1.5

> 1500 to ≤ 1800

0.0

0.0

Reflective

1.0

> 1800

0.0

0.0

Reflective

Reflective

> 0.6 to ≤ 0.7

0

X

X

X

X

> 0 to ≤ 300

X

X

X

X

> 300 to ≤ 450

X

X

X

X

> 450 to ≤ 600

Reflective

2.0

X

X

> 600 to ≤ 900

Reflective

1.0

2.0

X

> 900 to ≤ 1200

Reflective

Reflective

1.0

X

> 1200 to ≤ 1500

0.0

Reflective

Reflective

2.0

> 1500 to ≤ 1800

0.0

Reflective

Reflective

1.0

> 1800

0.0

0.0

Reflective

Reflective

Table Notes

SA = solar absorptance.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Reflective = reflective insulation with an airspace with a minimum width of at least 20 mm. The surface emittance of the reflective surface facing the airspace must be a maximum of 0.1, where the airspace is exposed to the sun during construction to reduce glare (an outward facing surface), or 0.05 if not exposed to the sun (an inward facing surface).

This table shows wall heights for single storey dwellings. For two storey (or more) dwellings with a wall height up to 2.4 m, add R0.5 to the R-Values given in this Table. For two storey (or more) dwellings with a wall height greater than 2.4 m, add R1.0.

Table 13.2.5b Lightweight walls – minimum insulation R-Value: climate zone 1

SA

Overhang (mm)

Wall height (m)

≤ 2.4

> 2.4 to ≤ 2.7

> 2.7 to ≤ 3.0

> 3.0 to ≤ 3.6

≤ 0.3

0

X

X

X

X

> 0 to ≤ 300

2.5

X

X

X

> 300 to ≤ 450

1.0

X

X

X

> 450 to ≤ 600

Reflective

2.0

X

X

> 600 to ≤ 900

Reflective

1.0

2.0

X

> 900 to ≤ 1200

Reflective

Reflective

1.0

X

> 1200 to ≤ 1500

Reflective

Reflective

Reflective

2.5

> 1500 to ≤ 1800

0.0

Reflective

Reflective

1.5

> 1800

0.0

0.0

Reflective

1.0

> 0.3 to ≤ 0.4

0

X

X

X

X

> 0 to ≤ 300

X

X

X

X

> 300 to ≤ 450

1.0

X

X

X

> 450 to ≤ 600

Reflective

2.0

X

X

> 600 to ≤ 900

Reflective

1.0

2.0

X

> 900 to ≤ 1200

Reflective

Reflective

1.0

X

>1200 to ≤ 1500

Reflective

Reflective

Reflective

2.5

> 1500 to ≤ 1800

0.0

Reflective

Reflective

1.5

> 1800

0.0

0.0

Reflective

1.0

> 0.4 to ≤ 0.5

0

X

X

X

X

> 0 to ≤ 300

X

X

X

X

> 300 to ≤ 450

1.0

X

X

X

> 450 to ≤ 600

Reflective

2.0

X

X

> 600 to ≤ 900

Reflective

1.0

2.0

X

> 900 to ≤ 1200

Reflective

Reflective

1.0

X

> 1200 to ≤ 1500

Reflective

Reflective

Reflective

2.5

> 1500 to ≤ 1800

0.0

Reflective

Reflective

1.5

> 1800

0.0

0.0

Reflective

1.0

> 0.5 to ≤ 0.6

0

X

X

X

X

> 0 to ≤ 300

X

X

X

X

> 300 to ≤ 450

1.0

X

X

X

> 450 to ≤ 600

Reflective

2.0

X

X

> 600 to ≤ 900

Reflective

1.0

2.0

X

> 900 to ≤ 1200

Reflective

Reflective

1.0

X

> 1200 to ≤ 1500

Reflective

Reflective

Reflective

2.5

> 1500 to ≤ 1800

0.0

Reflective

Reflective

1.5

> 1800

0.0

0.0

Reflective

1.0

> 0.6 to ≤ 0.7

0

X

X

X

X

> 0 to ≤ 300

X

X

X

X

> 300 to ≤ 450

1.0

X

X

X

> 450 to ≤ 600

Reflective

2.0

X

X

> 600 to ≤ 900

Reflective

1.0

2.0

X

> 900 to ≤ 1200

Reflective

Reflective

1.0

X

> 1200 to ≤ 1500

Reflective

Reflective

Reflective

2.5

> 1500 to ≤ 1800

0.0

Reflective

Reflective

1.5

> 1800

0.0

0.0

Reflective

1.0

Table Notes

SA = solar absorptance.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Reflective = reflective insulation with an airspace with a minimum width of at least 20 mm. The surface emittance of the reflective surface facing the airspace must be a maximum of 0.1 where the airspace is exposed to the sun during construction to reduce glare (an outward facing surface), or 0.05 of not exposed to the sun (an inward facing surface).

This Table shows wall heights for single storey dwellings. For two storey (or more) dwellings with a wall height up to 2.4 m, add R0.5 to R-Values from this Table. For two storey (or more) dwellings with a wall height greater than 2.4 m, add R1.0.

Table 13.2.5c Masonry veneer wall – minimum insulation R-Value: climate zone 2

SA

Overhang (mm)

Wall height (m)

≤ 2.4

> 2.4 to ≤ 2.7

> 2.7 to ≤ 3.0

> 3.0 to ≤ 3.6

≤ 0.35

0

X

X

X

X

> 0 to ≤ 300

2.0

X

X

X

> 300 to ≤ 450

1.5

X

X

X

> 450 to ≤ 600

1.5

2.0

X

X

> 600 to ≤ 900

1.5

1.5

2.5

X

> 900 to ≤ 1200

1.5

1.5

1.5

X

> 1200 to ≤ 1500

1.5

1.5

1.5

2.5

> 1500

1.5

1.5

1.5

2.0

> 0.35 to ≤ 0.5

0

X

X

X

X

> 0 to ≤ 300

2.0

X

X

X

> 300 to ≤ 450

1.5

X

X

X

> 450 to ≤ 600

1.5

2.5

X

X

> 600 to ≤ 900

1.5

1.5

2.5

X

> 900 to ≤ 1200

1.5

1.5

1.5

X

> 1200 to ≤ 1500

1.5

1.5

1.5

2.5

> 1500

1.5

1.5

1.5

2.0

> 0.5 to ≤ 0.7

0

X

X

X

X

> 0 to ≤ 300

2.0

X

X

X

> 300 to ≤ 450

1.5

X

X

X

> 450 to ≤ 600

1.5

2.0

X

X

> 600 to ≤ 900

1.5

1.5

2.5

X

> 900 to ≤ 1200

1.5

1.5

1.5

X

> 1200 to ≤ 1500

1.5

1.5

1.5

X

> 1500

1.5

1.5

1.5

2.0

Table Notes

SA = solar absorptance.

R-Valu

Tables

Changed since NCC 2022. See ABCB Housing Provisions 2022 13.2.5, or show what changed.

(1) Except for the external wall of a sub-floor space … 1500 to ≤ 1800 0.0 0.0 0.0 Reflective > 1800 to ≤ 2400 0.0 0.0 0.0 Reflective > 0.3 to ≤ 0.4 0 … 1500 to ≤ 1800 0.0 0.0 0.0 Reflective > 1800 to ≤ 2400 0.0 0.0 0.0 Reflective > 0.4 to ≤ 0.5 0 … 1500 to ≤ 1800 0.0 0.0 Reflective Reflective > 1800 to ≤ 2400 0.0 0.0 0.0 Reflective > 0.5 to ≤ 0.6 0 … 1500 to ≤ 1800 0.0 0.0 Reflective 1.0 > 1800 to ≤ 2400 0.0 0.0 Reflective Reflective > 0.6 to ≤ 0.7 0 … 1500 to ≤ 1800 0.0 Reflective Reflective 1.0 > 1800 to ≤ 2400 0.0 0.0 Reflective Reflective Table Notes SA = solar absorptance. … 1500 to ≤ 1800 0.0 Reflective Reflective 1.5 > 1800 to ≤ 2400 0.0 0.0 Reflective 1.0 > 0.3 to ≤ 0.4 0 … 1500 to ≤ 1800 0.0 Reflective Reflective 1.5 > 1800 to ≤ 2400 0.0 0.0 Reflective 1.0 > 0.4 to ≤ 0.5 0 … 1500 to ≤ 1800 0.0 Reflective Reflective 1.5 > 1800 to ≤ 2400 0.0 0.0 Reflective 1.0 > 0.5 to ≤ 0.6 0 … 1500 to ≤ 1800 0.0 Reflective Reflective 1.5 > 1800 to ≤ 2400 0.0 0.0 Reflective 1.0 > 0.6 to ≤ 0.7 0 … 1500 to ≤ 1800 0.0 Reflective Reflective 1.5 > 1800 to ≤ 2400 0.0 0.0 Reflective 1.0 Table Notes SA = solar absorptance. … 1200 to ≤ 1500 1.5 1.5 1.5 2.5 > 1500 to ≤ 1800 1.5 1.5 1.5 2.0 > 0.35 to ≤ 0.5 0 … 1200 to ≤ 1500 1.5 1.5 1.5 2.5 > 1500 to ≤ 1800 1.5 1.5 1.5 2.0 > 0.5 to ≤ 0.7 0 … to ≤ 900 1.5 1.5 2.5 X > 900 to ≤ 1200 1.5 1.5 1.5 X > 1200 to ≤ 1500 1.5 1.5 1.5 X > 1500 1.5 1.5 1.5 2.0 Table Notes SA = solar absorptance. R-Valu

Removed words are struck through; added words are highlighted. Comparison of the text only.

State and territory variations all clauses side by side →

Defined terms used