Table 13.2.5n Masonry cavity wall – minimum insulation R-Value: climate zone 7

Part 13.2 Building fabric

Open Table 13.2.5n on NCC Online ↗
SAOverhang (mm)Wall height (m)
≤ 2.4> 2.4 to ≤ 2.7> 2.7 to ≤ 3.0> 3.0 to ≤ 3.6
≤ 0.3501.081.44XX
> 0.35 to ≤ 0.501.081.44XX
> 0.5 to ≤ 0.700.751.441.44X
> 0 to ≤ 3001.44XXX
> 0.7 to ≤ 0.8500.751.081.44X
> 0 to ≤ 3001.441.44XX

Table Notes

SA = solar absorptance.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

This Table shows wall heights for single storey dwellings. For two storey (or more) dwellings, add R0.25 to the R-Values given in this Table.

Where an overhang of > 300 mm is used, the values for > 0 to ≤ 300 apply provided no more than 15% of the total opaque wall area of the dwelling (excluding windows/doors) is covered by overhangs > 300 mm.

Table for 13.2.5 External walls

Changed since NCC 2022. See ABCB Housing Provisions 2022 Table 13.2.5n, or show what changed.

SA | Overhang (mm) | Wall height (m) ≤ 2.4 … dwellings, add R0.25 to the R-Values given in this Table. Where an overhang of > 300 mm is used, the values for > 0 to ≤ 300 apply provided no more than 15% of the total opaque wall area of the dwelling (excluding windows/doors) is covered by overhangs > 300 mm.

Removed words are struck through; added words are highlighted. Comparison of the text only.