Table · ABCB Housing Provisions 2025

Table 13.2.5q Lightweight metal-framed walls: minimum Total R-Value to account for thermal bridging

Part 13.2 Building fabric

Open Table 13.2.5q on NCC Online ↗
Wall insulation R-Value required in accordance with 13.2.5(2)Minimum Total R-Value to account for thermal bridging
1.01.32
1.51.64
2.01.89
2.52.06
2.72.15
≥3.02.27

Table Notes

Where the wall insulation R-Value from Tables 13.2.5b, 13.2.5c, 13.2.5d, 13.2.5e, 13.2.5f, 13.2.5g, 13.2.5h, 13.2.5i, 13.2.5j, 13.2.5k, 13.2.5l, 13.2.5m, 13.2.5n and 13.2.5o falls between the values shown in this Table, the required Total R-Value may be interpolated.

Minimum Total R-Values are in-situ values. They account for compression of insulation.

Table for 13.2.5 External walls

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.5q.