Table · ABCB Housing Provisions 2025
Table 13.2.5q Lightweight metal-framed walls: minimum Total R-Value to account for thermal bridging
| Wall insulation R-Value required in accordance with 13.2.5(2) | Minimum Total R-Value to account for thermal bridging |
|---|---|
| 1.0 | 1.32 |
| 1.5 | 1.64 |
| 2.0 | 1.89 |
| 2.5 | 2.06 |
| 2.7 | 2.15 |
| ≥3.0 | 2.27 |
Table Notes
Where the wall insulation R-Value from Tables 13.2.5b, 13.2.5c, 13.2.5d, 13.2.5e, 13.2.5f, 13.2.5g, 13.2.5h, 13.2.5i, 13.2.5j, 13.2.5k, 13.2.5l, 13.2.5m, 13.2.5n and 13.2.5o falls between the values shown in this Table, the required Total R-Value may be interpolated.
Minimum Total R-Values are in-situ values. They account for compression of insulation.
Table for 13.2.5 External walls
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.5q.