Table 13.2.6g Minimum R-Value of floor and subfloor insulation where the floor is over an enclosed subfloor space: climate zone 7
| Subfloor wall height (mm) | Reflective insulation facing down over the subfloor space | Minimum subfloor wall insulation R-Value | Minimum suspended floor insulation R-Value |
|---|---|---|---|
| ≤600 | No | 0.0 | 2.5 |
| ≤600 | Yes | 0.0 | 1.5 |
| >600 to ≤900 | No | 0.0 | 2.5 |
| >600 to ≤900 | Yes | 0.0 | 1.5 |
| >900 to ≤1200 | No | 0.0 | 3.0 |
| >900 to ≤1200 | Yes | 0.0 | 1.5 |
| >1200 to ≤1500 | No | 0.0 | 3.0 |
| >1200 to ≤1500 | Yes | 0.0 | 1.5 |
| >1500 to ≤1800 | No | 0.0 | 3.0 |
| >1500 to ≤1800 | Yes | 1.0 | 1.5 |
| >1500 to ≤1800 | Yes | 0.0 | 2.0 |
Table Notes
A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.
R-Values listed are for the labelled, declared R-Value of insulation.
Table for 13.2.6 Floors and subfloor walls
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 13.2.6g.