13.2.6 Floors and subfloor walls
Part 13.2 Building fabric · NCC 2019: NSW 3.12.1.1, 3.12.1.5
(1) Floor insulation, where the floor is over an unenclosed space, must achieve the minimum R-Value in accordance with Table 13.2.6a.
(2) Floor and subfloor insulation, where the floor is over an enclosed subfloor space, must—
in climate zone 1, be subfloor wall insulation with an R-Value of R1.5; and
in climate zone 2, be subfloor wall insulation in accordance with Table 13.2.6b; and
in climate zone 3, be subfloor wall insulation in accordance with Table 13.2.6c; and
in climate zone 4, be in accordance with Table 13.2.6d; and
in climate zone 5, be in accordance with Table 13.2.6e; and
in climate zone 6, be in accordance with Table 13.2.6f; and
in climate zone 7, be in accordance with Table 13.2.6g; and
in climate zone 8, be in accordance with Table 13.2.6h.
(3) The thermal bridging in a metal-framed floor must be addressed by—
achieving the Total R-Value in Table 13.2.6i, calculated by—
using a method that accounts for the effect of thermal bridging in a suspended floor above an enclosed subfloor space; or
using AS/NZS 4859.2 for all other floors; or
complying with one of the options in Table 13.2.6j.
(4) A concrete slab-on-ground with an in-slab or in-screed heating or cooling system, must have insulation with an R-Value greater than or equal to 1.0, installed around the vertical edge of its perimeter.
(5) A concrete slab-on-ground or the like, other than a waffle pod slab, must be insulated in accordance with the following:
In climate zones 6 and 7—
insulation with R-Value greater than or equal to 0.64 must be installed around the vertical edge of its perimeter; and
insulation with an R-Value greater than or equal to 0.64 must be installed underneath the slab.
In climate zone 8—
insulation with an R-Value greater than or equal to 1.0 must be installed around the vertical edge of its perimeter; and
insulation with an R-Value greater than or equal to 2.0 must be installed underneath the slab.
(6) Insulation required by (4), (5)(a)(i) and (5)(b)(i) must—
be water resistant; and
be continuous from the adjacent finished ground level—
to a depth of greater than or equal to 300 mm; or
for at least the full depth of the vertical edge of the concrete slab-on-ground (see Figure 13.2.6).
(7) The requirements of (4) do not apply to an in-screed heating or cooling system used solely in a bathroom, amenity area or the like.
Table 13.2.6a Minimum R-Value of floor insulation where the floor is over an unenclosed space
Climate zone
R-Value
1
2.0
2
2.0
3
1.5
4
X
5
X
6
4.0, or 3.5 if used in conjunction with a reflective airspace
7
8
Table Notes
R-Values listed are for the labelled, declared R-Value of insulation.
X = not permitted.
Table 13.2.6b Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 2
Subfloor wall height (mm)
Minimum subfloor wall insulation R-Value
≤600
0.5
>600 to ≤900
1.0
>900 to ≤1200
1.5
>1200 to ≤1500
1.5
>1500 to ≤1800
1.5
Table Notes
Under-floor insulation is not permitted in climate zone 2.
R-Values listed are for the labelled, declared R-Value of insulation.
Subfloor wall insulation must not obstruct ventilation openings in the subfloor walls.
Table 13.2.6c Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 3
Subfloor wall height (mm)
Minimum subfloor wall insulation R-Value
≤600
0.5
>600 to ≤900
0.5
>900 to ≤1200
0.5
>1200 to ≤1500
0.5
>1500 to ≤1800
0.5
Table Notes
Under-floor insulation is not permitted in climate zone 3.
R-Values listed are for the labelled, declared R-Value of insulation.
Subfloor wall insulation must not obstruct any ventilation openings in subfloor walls.
Table 13.2.6d Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 4
Subfloor wall height (mm)
Reflective insulation facing down over the subfloor space
Minimum subfloor wall insulation R-Value
Minimum suspended floor insulation R-Value
≤600
No
0.5
1.0
≤600
No
1.0
0.5
≤600
Yes
0.0
1.5
≤600
Yes
0.5
1.0
≤600
Yes
2.0
0.5
>600 to ≤900
No
0.0
1.5
>600 to ≤900
No
1.5
0.5
>600 to ≤900
Yes
0.0
1.5
>600 to ≤900
Yes
0.5
1.0
>900 to ≤1200
No
0.0
1.5
>900 to ≤1200
No
0.5
1.0
>900 to ≤1200
Yes
0.5
1.0
>900 to ≤1200
Yes
2.0
0.5
>1200 to ≤1500
No
0.0
1.5
>1200 to ≤1500
Yes
0.0
1.5
>1200 to ≤1500
Yes
0.5
1.0
>1500 to ≤1800
No
0.5
1.5
>1500 to ≤1800
No
1.0
1.0
>1500 to ≤1800
Yes
0.0
2.0
Table Notes
A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.
R-Values listed are for the labelled, declared R-Value of insulation.
Table 13.2.6e Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor area: climate zone 5
Subfloor wall height (mm)
Reflective insulation facing down over the subfloor surface
Minimum subfloor wall insulation R-Value
Minimum suspended floor insulation R-Value
≤600
No
0.0
1.5
≤600
Yes
0.0
2.0
>600 to ≤900
No
0.0
1.5
>600 to ≤900
Yes
0.0
2.0
>900 to ≤1200
No
0.0
2.0
>900 to ≤1200
Yes
0.0
2.0
>1200 to ≤1500
No
0.0
2.0
>1200 to ≤1500
Yes
0.0
2.0
>1500 to ≤1800
No
0.0
2.5
>1500 to ≤1800
No
0.5
2.0
>1500 to ≤1800
Yes
0.0
2.5
>1500 to ≤1800
Yes
0.5
2.0
Table Notes
A suspended floor includes a suspended timber-framed floor, a suspended metal-framed floor and a suspended concrete floor.
R-Values listed are for the labelled, declared R-Value of insulation.
Table 13.2.6f Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 6
Subfloor wall height (mm)
Reflective insulation facing down over the subfloor area
Minimum subfloor wall insulation R-Value
Minimum suspended floor insulation R-Value
≤600
No
0.0
2.0
≤600
Yes
0.0
1.5
>600 to ≤900
No
0.0
2.0
>600 to ≤900
Yes
0.0
1.5
>900 to ≤1200
No
0.0
2.0
>900 to ≤1200
Yes
0.0
1.5
>1200 to ≤1500
No
0.0
2.5
>1200 to ≤1500
No
0.5
2.0
>1200 to ≤1500
Yes
0.0
1.5
>1500 to ≤1800
No
0.0
2.5
>1500 to ≤1800
Yes
0.0
2.0
>1500 to ≤1800
Yes
0.5
1.5
Table Notes
A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.
R-Values listed are for the labelled, declared R-Value of insulation.
Table 13.2.6g Minimum R-Value of floor and subfloor insulation where the floor is over an enclosed subfloor space: climate zone 7
Subfloor wall height (mm)
Reflective insulation facing down over the subfloor space
Minimum subfloor wall insulation R-Value
Minimum suspended floor insulation R-Value
≤600
No
0.0
2.5
≤600
Yes
0.0
1.5
>600 to ≤900
No
0.0
2.5
>600 to ≤900
Yes
0.0
1.5
>900 to ≤1200
No
0.0
3.0
>900 to ≤1200
Yes
0.0
1.5
>1200 to ≤1500
No
0.0
3.0
>1200 to ≤1500
Yes
0.0
1.5
>1500 to ≤1800
No
0.0
3.0
>1500 to ≤1800
Yes
1.0
1.5
>1500 to ≤1800
Yes
0.0
2.0
Table Notes
A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.
R-Values listed are for the labelled, declared R-Value of insulation.
Table 13.2.6h Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 8
Subfloor wall height (mm)
Reflective insulation facing down over the subfloor space
Minimum subfloor wall insulation R-Value
Minimum suspended floor insulation R-Value
≤600
No
0.0
2.5
≤600
Yes
0.0
1.5
>600 to ≤900
No
0.0
2.5
>600 to ≤900
Yes
0.0
1.5
>900 to ≤1200
No
0.0
3.0
>900 to ≤1200
Yes
0.0
1.5
>1200 to ≤1500
No
0.0
3.0
>1200 to ≤1500
Yes
0.0
1.5
>1500 to ≤1800
No
0.0
3.0
>1500 to ≤1800
Yes
1.0
1.5
>1500 to ≤1800
Yes
0.0
2.0
Table Notes
A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.
R-Values listed are for the labelled, declared R-Value of insulation.
Table 13.2.6i Metal-framed suspended floor — minimum Total R-Value for floor to account for thermal bridging
Floor insulation from Tables 13.2.6a and 13.2.6d to 13.2.6h as applicable
Floor covering
Minimum Total R-Value of floor
0.0
Carpet
0.36
0.0
Other
Tables
- Table 13.2.6a Minimum R-Value of floor insulation where the floor is over an unenclosed space
- Table 13.2.6b Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 2
- Table 13.2.6c Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 3
- Table 13.2.6d Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 4
- Table 13.2.6e Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor area: climate zone 5
- Table 13.2.6f Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 6
- Table 13.2.6g Minimum R-Value of floor and subfloor insulation where the floor is over an enclosed subfloor space: climate zone 7
- Table 13.2.6h Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 8
- Table 13.2.6i Metal-framed suspended floor — minimum Total R-Value for floor to account for thermal bridging
- Table 13.2.6j Metal-framed suspended floor — thermal bridging mitigation
- Table 13.2.6k Floor — direction of heat flow
Changed since NCC 2022. See ABCB Housing Provisions 2022 13.2.6, or show what changed.
(1) Floor insulation, where the floor is over an unenclosed … 1.0, installed around the vertical edge of its perimeter. (5) Except for A concrete slab-on-ground or the like, other than a waffle-pod slab — waffle pod slab, must be insulated in accordance with the following: In climate zones 6 and 7 — insulation with R-Value greater … than or equal to 0.64 must be installed underneath the slab; and in slab. In climate zone 8 — insulation with an R-Value greater than … Minimum Total R-Value of floor 0.0 Carpet 0.36 0.0 Other 0.22 0.5 Carpet 0.86 0.5 Other 0.71 1.0 Carpet 1.30 1.0 Other 1.15 1.5 Carpet 1.65 1.5
Removed words are struck through; added words are highlighted. Comparison of the text only.