Table · ABCB Housing Provisions 2025
Table 5.4.2b Return support limitations for external single leaf masonry walls to AS 3700
Part 5.4 Unreinforced single leaf masonry
| Element | Symbol used in Figure 5.4.2c | Thickness of wall (T) | |||
|---|---|---|---|---|---|
| 90 | 110 | 140 | 190 | ||
| Return length (minimum) | R | 450 | 450 | – | – |
| Spacing of returns (maximum) (N2) | S | 1050 | 1300 | – | – |
| Spacing of returns (maximum) (N3) | S | 600 | 750 | – | – |
| Height (maximum) | H | 2400 | 2400 | 1700 (N2) | 2300 (N2) |
Table Notes
Dimensions are in mm.
Return supports are not required for 140 mm and 190 mm thick walls.
Table for 5.4.2 External walls
Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 5.4.2b.