Part 5.4 Unreinforced single leaf masonry
9 clauses · Open on NCC Online ↗
- 5.4.1 Application of Part 5.4Part 5.4 applies subject to the limitations set out in H1D5(3)(c). (2) Part 5.4 need not be complied with if H1D5(3)(a) or (b) are complied with.
- Table 5.4.2a Engaged piers in external single leaf masonry walls to AS 3700Element | Symbol used in Figure 5.4.2b | Thickness of wall (T) 90 | 110 Pier size (minimum) (not more than N2) | A x B | 290 x 190 (800 spacing) |…
- Table 5.4.2b Return support limitations for external single leaf masonry walls to AS 3700Element | Symbol used in Figure 5.4.2c | Thickness of wall (T) 90 | 110 | 140 | 190 Return length (minimum) | R | 450 | 450 | – | – Spacing of…
- Table 5.4.2c Engaged piers in external walls of Class 10a buildings — wall height: 2.4 mWall thickness (mm) | Pier thickness (mm) | Pier width (mm) | Spacing (mm) for wind class N1 | N2 90 | 190 | 290 | 1000 | 600 90 | 290 | 190 | 1700…
- Table 5.4.2d Engaged piers in external walls of Class 10a building — wall height: 2.7 mWall thickness (mm) | Pier thickness (mm) | Pier width (mm) | Spacing (mm) for wind class N1 | N2 90 | 190 | 290 | 700 | 500 90 | 290 | 190 | 1300 |…
- 5.4.2 External wallsSingle leaf unreinforced masonry walls with engaged piers and return walls must comply with the relevant provisions of this Part and be constructed…
- 5.4.3 Internal wallsInternal masonry walls must be engaged with other walls, must comply with the relevant provisions of this Part and must be— not less than 75 mm…
- 5.4.4 Vertical articulation jointsVertical articulation joints must be provided in accordance with 5.6.8.
- 5.4.5 Damp-proof courses and flashing materialsWhere required, damp-proof courses and flashing must be provided in accordance with 5.7.3 and 5.7.4.