Table · ABCB Housing Provisions 2025

Table 6.3.4j Maximum counter-strutting beam span — counter-strutting beam supporting tiled roof and plasterboard ceiling — roof load area = 4 m2

Part 6.3 Structural steel members

Open Table 6.3.4j on NCC Online ↗
SectionCeiling load area (m2)
0612
125 TFB3.43.12.9
150 UB 14.03.53.33.0
200 UB 18.24.74.44.1
250 UB 31.47.97.47.0
310 UB 46.210.910.49.9
100 TFB1.71.61.4
150 PFC5.14.63.6
200 PFC6.25.75.4
250 PFC9.08.48.0
300 PFC9.58.98.5

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.

Table for 6.3.4 Strutting beams

Same wording in ABCB Housing Provisions 2022. See ABCB Housing Provisions 2022 Table 6.3.4j.