ABCB Housing Provisions 2025
Part 6.3 Structural steel members
41 clauses · Open on NCC Online ↗
- 6.3.1 ApplicationPart 6.3, other than clause 6.3.4, applies subject to the limitations set out in H1D6(6). (2) Part 6.3 need not be complied with if H1D6(5)(a) or…
- 6.3.2 Structural steel membersStructural steel members may be used as follows: Bearers supporting a timber floor or non-load bearing stud wall — in accordance with 6.3.3.…
- Table 6.3.3a Maximum bearer span (m) — single span — bearer supporting timber floor and 3 m high non-loadbearing internal wallSteel section | Effective load width (m) 1.8 | 2.4 | 3.0 | 3.6 | 4.2 125 TFB | 4.2 | 4.0 | 3.9 | 3.8 | 3.6 180 UB 16.1 | 5.6 | 5.4 | 5.3 | 5.1 | 4.7…
- Table 6.3.3b Maximum bearer span (m) — continuous span — bearer supporting timber floor and 3 m high non-loadbearing internal wallSteel section | Effective load width (m) 1.8 | 2.4 | 3.0 | 3.6 | 4.2 125 TFB | 5.2 | 4.6 | 4.2 | 3.9 | 3.6 180 UB 16.1 | 6.8 | 6.0 | 5.5 | 5.1 | 4.7…
- Table 6.3.3c Maximum bearer span (m) — single span — bearer supporting tiled floor and 3 m high non-loadbearing internal wallSteel section | Effective load width (m) 1.8 | 2.4 | 3.0 | 3.6 | 4.2 125 TFB | 3.9 | 3.7 | 3.5 | 3.4 | 3.3 180 UB 16.1 | 5.2 | 5.0 | 4.8 | 4.6 | 4.4…
- Table 6.3.3d Maximum bearer span (m) — continuous span — bearer supporting tiled floor and 3 m high non-loadbearing internal wallSteel section | Effective load width (m) 1.8 | 2.4 | 3.0 | 3.6 | 4.2 125 TFB | 4.8 | 4.3 | 3.9 | 3.6 | 3.3 180 UB 16.1 | 6.3 | 5.6 | 5.1 | 4.7 | 4.4…
- 6.3.3 BearersStructural steel bearers must comply with the following: Effective bearer spacing must be determined in accordance with— for single span joists —…
- Table 6.3.4a Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting metal sheet roof and plasterboard ceiling — roof load area = 4 m2Section | Ceiling load width (m) 1.8 | 3.6 | 6.0 125 TFB | 3.5 | 3.3 | 3.2 150 UB 14.0 | 3.6 | 3.4 | 3.3 200 UB 18.2 | 4.5 | 4.3 | 4.1 250 UB 31.4 |…
- Table 6.3.4b Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting metal sheet roof and plasterboard ceiling — roof load area = 8 m2Section | Ceiling load width (m) 1.8 | 3.6 | 6.0 125 TFB | 2.6 | 2.6 | 2.5 150 UB 14.0 | 2.8 | 2.7 | 2.7 200 UB 18.2 | 3.6 | 3.5 | 3.4 250 UB 31.4 |…
- Table 6.3.4c Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting metal sheet roof and plasterboard ceiling — roof load area = 12 m2Section | Ceiling load width (m) 1.8 | 3.6 | 6.0 125 TFB | 2.2 | 2.2 | 2.2 150 UB 14.0 | 2.4 | 2.3 | 2.3 200 UB 18.2 | 3.1 | 3.0 | 3.0 250 UB 31.4 |…
- Table 6.3.4d Maximum counter-strutting beam span — counter-strutting beam supporting metal sheet roof and plasterboard ceiling — roof load area = 4 m2Section | Ceiling load area (m2) 0 | 6 | 12 125 TFB | 3.9 | 3.5 | 3.2 150 UB 14.0 | 4.0 | 3.7 | 3.4 200 UB 18.2 | 5.4 | 4.9 | 4.6 250 UB 31.4 | 8.9…
- Table 6.3.4e Maximum counter-strutting beam span — counter-strutting beam supporting metal sheet roof and plasterboard ceiling — roof load area = 8 m2Section | Ceiling load area (m2) 0 | 6 | 12 125 TFB | 2.7 | 2.6 | 2.4 150 UB 14.0 | 2.9 | 2.8 | 2.6 200 UB 18.2 | 4.0 | 3.8 | 3.6 250 UB 31.4 | 6.8…
- Table 6.3.4f Maximum counter-strutting beam span — counter-strutting beam supporting metal sheet roof and plasterboard ceiling — roof load area = 12 m2Section | Ceiling load area (m2) 0 | 6 | 12 125 TFB | 2.2 | 2.1 | 2.0 150 UB 14.0 | 2.4 | 2.3 | 2.2 200 UB 18.2 | 3.3 | 3.2 | 3.0 250 UB 31.4 | 5.7…
- Table 6.3.4g Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting tiled roof and plasterboard ceiling — roof load area = 4 m2Section | Ceiling load width (m) 1.8 | 3.6 | 6.0 125 TFB | 2.7 | 2.6 | 2.6 150 UB 14.0 | 2.8 | 2.8 | 2.7 200 UB 18.2 | 3.6 | 3.5 | 3.4 250 UB 31.4 |…
- Table 6.3.4h Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting tiled roof and plasterboard ceiling — roof load area = 8 m2Section | Ceiling load width (m) 1.8 | 3.6 | 6.0 125 TFB | 2.0 | 2.0 | 2.0 150 UB 14.0 | 2.2 | 2.1 | 2.1 200 UB 18.2 | 2.8 | 2.8 | 2.7 250 UB 31.4 |…
- Table 6.3.4i Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting tiled roof and plasterboard ceiling — roof load area = 12 m2Section | Ceiling load width (m) 1.8 | 3.6 | 6.0 125 TFB | 1.7 | 1.7 | 1.7 150 UB 14.0 | 1.8 | 1.8 | 1.8 200 UB 18.2 | 2.4 | 2.4 | 2.4 250 UB 31.4 |…
- Table 6.3.4j Maximum counter-strutting beam span — counter-strutting beam supporting tiled roof and plasterboard ceiling — roof load area = 4 m2Section | Ceiling load area (m2) 0 | 6 | 12 125 TFB | 3.4 | 3.1 | 2.9 150 UB 14.0 | 3.5 | 3.3 | 3.0 200 UB 18.2 | 4.7 | 4.4 | 4.1 250 UB 31.4 | 7.9…
- Table 6.3.4k Maximum counter-strutting beam span — counter-strutting beam supporting tiled roof and plasterboard ceiling — roof load area = 8 m2Section | Ceiling load area (m2) 0 | 6 | 12 125 TFB | 2.3 | 2.2 | 2.1 150 UB 14.0 | 2.5 | 2.4 | 2.3 200 UB 18.2 | 3.4 | 3.3 | 3.2 250 UB 31.4 | 5.9…
- Table 6.3.4l Maximum counter-strutting beam span — counter-strutting beam supporting tiled roof and plasterboard ceiling — roof load area = 12 m2Section | Ceiling load area (m2) 0 | 6 | 12 125 TFB | 1.8 | 1.8 | 1.7 150 UB 14.0 | 2.0 | 1.9 | 1.9 200 UB 18.2 | 2.8 | 2.7 | 2.7 250 UB 31.4 | 5.0…
- 6.3.4 Strutting beamsStructural steel strutting beams must comply with the following: Acceptable strutting beam spacing must be determined in accordance with— for single…
- Table 6.3.5a Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 1.5 mSection | Floor load width (m) 0 | 1.8 | 3.6 150 UB 14.0 | 4.4 | 3.0 | 2.5 200 UB 25.4 | 6.8 | 4.7 | 4.0 250 UB 31.4 | 7.7 | 5.3 | 4.6 100 TFB | 2.8…
- Table 6.3.5b Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 4.5 mSection | Floor load width (m) 0 | 1.8 | 3.6 150 UB 14.0 | 3.1 | 2.7 | 2.4 200 UB 25.4 | 4.9 | 4.3 | 3.8 250 UB 31.4 | 5.6 | 4.9 | 4.3 100 TFB | 1.9…
- Table 6.3.5c Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 7.5 mSection | Floor load width (m) 0 | 1.8 | 3.6 150 UB 14.0 | 2.6 | 2.4 | 2.2 200 UB 25.4 | 4.1 | 3.8 | 3.6 250 UB 31.4 | 4.7 | 4.4 | 4.1 100 TFB | 1.6…
- Table 6.3.5d Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 1.5 mSection | Floor load width (m) 0 | 1.8 | 3.6 150 UB 14.0 | 4.0 | 2.8 | 2.3 200 UB 25.4 | 6.2 | 4.4 | 3.7 250 UB 31.4 | 7.1 | 5.0 | 4.3 100 TFB | 2.5…
- Table 6.3.5e Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 4.5 mSection | Floor load width (m) 0 | 1.8 | 3.6 150 UB 14.0 | 2.8 | 2.5 | 2.2 200 UB 25.4 | 4.4 | 3.9 | 3.5 250 UB 31.4 | 5.1 | 4.5 | 4.0 100 TFB | 1.7…
- Table 6.3.5f Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 7.5 mSection | Floor load width (m) 0 | 1.8 | 3.6 150 UB 14.0 | 2.4 | 2.2 | 2.0 200 UB 25.4 | 3.8 | 3.4 | 3.2 250 UB 31.4 | 4.3 | 4.0 | 3.7 100 TFB | 1.5…
- 6.3.5 LintelsStructural steel lintels must comply with the following: Spans for lintels supporting roofs, frames and timber floors must be determined in…
- Table 6.3.6a Required column section — columns supporting tiled floor and tiled roof load — roof load area = 0 m2Column section | Effective height (mm) | Floor load area (m2) 4 | 10 | 16 CHS 250 | 2400 | 60.3 x 4.5 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS CHS 250 |…
- Table 6.3.6b Required column section — columns supporting tiled floor and tiled roof load — roof load area = 9 m2Column section | Effective height (mm) | Floor load area (m2) 4 | 10 | 16 CHS 250 | 2400 | 76.1 x 4.5 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS CHS 250…
- Table 6.3.6c Required column section — columns supporting tiled floor and tiled roof load — roof load area = 18 m2Column section | Effective height (mm) | Floor load area (m2) 4 | 10 | 16 CHS 250 | 2400 | 88.9 x 5 CHS | 114.3 x 5.4 CHS | 139.7 x 5 CHS CHS 250 |…
- Table 6.3.6d Required column section — columns supporting timber floor and metal roof load — roof load area = 0 m2Column section | Effective height (mm) | Floor load area (m2) 4 | 10 | 16 CHS 250 | 2400 | 60.3 x 3.6 CHS | 76.1 x 5.9 CHS | 101.6 x 5 CHS CHS 250 |…
- Table 6.3.6e Required column section — columns supporting timber floor and metal roof load — roof load area = 9 m2Column section | Effective height (mm) | Floor load area (m2) 4 | 10 | 16 CHS 250 | 2400 | 60.3 x 5.4 CHS | 88.9 x 5 CHS | 114.3 x 4.5 CHS CHS 250 |…
- Table 6.3.6f Required column section — columns supporting timber floor and metal roof load — roof load area = 18 m2Column section | Effective height (mm) | Floor load area (m2) 4 | 10 | 16 CHS 250 | 2400 | 76.1 x 4.5 CHS | 101.6 x 5 CHS | 114.3 x 5.4 CHS CHS 250…
- Table 6.3.6g Area supported by columnsColumn descriptor (as shown in Figure 6.3.6a) | Total area supported C1 | 0.4L1 x 0.4LA C2 | 0.7(L1 + L2) x 0.4LA C3 | 0.4L1 x 0.7(LA + LB) C4 |…
- 6.3.6 ColumnsStructural steel columns must comply with the following: Columns must support the maximum area provided for in— Tables 6.3.6a, 6.3.6b and 6.3.6c for…
- 6.3.7 Fixings and bearing for structural steel membersAll bolts used in connections must be hot dip galvanised 300 g/m2. (2) Bearer connections must be fixed in accordance with Figure 6.3.7a. (3)…
- 6.3.8 Penetrations through structural steel membersPenetrations through structural steel members must be within the allowable zones in Figure 6.3.8. Figure 6.3.8 Allowable zones for penetrations…
- Table 6.3.9a Minimum protective coatings for structural steel membersEnvironment | Location | Minimum protective coating Option 1 (hot dip galvanising) | Option 2 (duplex system). See Table 6.3.9c | Option 3 (paint).…
- Table 6.3.9b Paint coating system specificationAS 2312.1 system | Surface preparation | 1st coat | 2nd coat | 3rd coat | Total DFT Type of paint | DFT | Type of paint | DFT | Type of paint | DFT…
- Table 6.3.9c Duplex coating system specificationAS 2312.2 duplex system | Surface preparation | 1st coat | 2nd coat | 3rd coat | Total DFT Type of paint | DFT | Type of paint | DFT | Type of paint…
- 6.3.9 Corrosion protectionStructural steel members that are not built in to a masonry wall must— be protected against corrosion in accordance with Tables 6.3.9a, 6.3.9b and…