B2P5 Isolation
Part B2 Heated water services · NCC 2019: BP2.4
Means of isolation must be provided to a heated water service and components that require testing, maintenance and replacement including mechanical devices, appliances and controls.
Changed since NCC 2022. See NCC 2022 Volume Three B2P5, or show what changed.
Containers used for producing and/or storing Means of isolation must be provided to a heated water are to relieve excessive pressure service and avoid flash steam production by — relieving pressure so components that the maximum rated working pressure, or 1400 kPa, whichever is the lesser, is not exceeded; require testing, maintenance and limiting water temperatures to a maximum of 99 °C; or other suitable means providing an equivalent level of safety to (a) replacement including mechanical devices, appliances and (b). Applications B2P5(a) has a tolerance of +5% or 14 kPa whichever is the greater. controls.
Removed words are struck through; added words are highlighted. Comparison of the text only.