NCC 2025 Volume Three
Part B2 Heated water services
31 clauses · Open on NCC Online ↗
- B2O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a heated water…
- B2F1 Heated water supplySanitary fixtures, sanitary appliances and supply outlets provided with heated water must have a safe and adequate piped heated water supply.
- B2F2 Heated water installationsThe heated water supply must be conveyed through plumbing installations in a way that— minimises any adverse impact on building occupants, the…
- B2F3 Greenhouse gas emissionsTo reduce greenhouse gas emissions, to the degree necessary, a heated water service is to— be capable of efficiently using energy; and obtain its…
- B2P1 Heated water supplyA heated water service must be connected to a drinking water supply. Applications B2P1 applies to a heated water service used for human consumption,…
- B2P2 Scald preventionHeated water supplied by a heated water service must be delivered from the point of discharge of fixtures and appliances at a temperature which is…
- B2P3 VelocityThe water velocity in heated water service pipework up to 65 °C must not exceed— 3.0 m/s for no less than 99% of the time that water is required…
- B2P4 AccessAccess must be provided to components of a heated water service that require maintenance or replacement, including mechanical devices and controls.
- B2P5 IsolationMeans of isolation must be provided to a heated water service and components that require testing, maintenance and replacement including mechanical…
- B2P6 Pressure relief and temperature limitationContainers used for producing and/or storing heated water are to relieve excessive pressure and avoid flash steam production by— relieving pressure…
- B2P7 Legionella controlHeated water must be stored and delivered under conditions which avoid the likelihood of the growth of a Legionella bacteria count greater than or…
- B2P8 Energy use and source NSW QLDA heated water service, including any associated distribution system and components, must ensure the efficient use of energy and water. (2) Features…
- B2P9 TemperatureHeated water from a heated water service must be provided at appropriate temperatures for the correct functioning of fixtures or appliances.
- B2P10 Pressure TASThe points of discharge for a heated water service must— have— a working pressure of not less than 50 kPa; and a static pressure within the building…
- B2P11 Uncontrolled dischargeAny failure or uncontrolled discharge from a heated water service must be avoided.
- B2P12 Water efficiency NSWA heated water service must ensure the efficient use of drinking water by limiting water use from a tap or outlet for a shower, basin, kitchen sink…
- Table B2V1 Heated water storage minimum exposure periodTemperature | Minimum exposure period 70 °C or greater | 1 second 66 °C | 2 minutes 60 °C | 32 minutes
- B2V1 Heated water storage temperatureCompliance with B2P6 is verified for each heated water storage system when the water heater is designed such that all water is subjected to a…
- B2D1 Deemed-to-Satisfy ProvisionsPerformance Requirement B2P1 is satisfied if heated water is supplied by— the Network Utility Operator’s drinking water supply; or an alternative…
- Table B2D2a Minimum Small Scale Technology CertificatesNumber of bedrooms in the building | 2025 | 2026 | 2027 | 2028 1 or 2 | 8 | 7 | 5 | 4 3 or 4 | 13 | 11 | 8 | 6 4 or more | 16 | 14 | 11 | 8
- Table B2D2b Minimum energy savingsNumber of bedrooms | Minimum energy saving 1 or 2 | 40% for a ‘small load’ system 2 or 3 | 60% for a ‘medium load’ system 4 or more | 60% for a…
- B2D2 Water heater in a heated water supply system NSW QLD SA TASIn a new Class 1 or Class 10 building, a water heater in a heated water supply system must be— a solar water heater complying with (2); or a heat…
- B2D3 Layout of tapsWhere both a heated water tap and a cold water tap are installed, the heated water tap must be installed to the left of, or above, the cold water…
- B2D4 Water efficiency NSWA tap or outlet used for a shower, basin, kitchen sink, or laundry trough must be a minimum of 3 Star WELS rated and discharge not more than 9…
- B2D5 Maximum delivery temperature NSW SA WAThe delivery temperature of heated water at the outlet of each sanitary fixture must be— not more than 45 °C in any— residential part of an aged…
- B2D6 Temperature control devices NSW TAS WAA temperature control device used to deliver heated water in accordance with B2D5(a) must be a— thermostatic mixing valve; or thermostatically…
- B2D7 Heated water storageContainers used for producing and/or storing heated water must be provided with a temperature and pressure relief device in accordance with AS/NZS…
- B2D8 Legionella controlLegionella control for water heaters must be carried out in accordance with AS/NZS 3500.4.
- B2D9 General requirements NSW SA WAA heated water service must be in accordance with AS/NZS 3500.4.
- B2D10 Bushfire prone areasA heated water service in a designated bushfire prone area must be in accordance with AS 3959.
- B2D11 Solar heated waterA solar heated water supply system for food preparation and sanitary purposes, where installed in a new building in climate zones 1, 2 or 3, is not…