Verification Method · NCC 2025 Volume Three

B2V1 Heated water storage temperature

Part B2 Heated water services · NCC 2019: BV2.2

Open B2V1 on NCC Online ↗

Compliance with B2P6 is verified for each heated water storage system when the water heater is designed such that all water is subjected to a temperature-dependent minimum exposure period as specified in Table B2V1 within 7 days before passing through the water-heating appliance's heated water outlet.

Table B2V1 Heated water storage minimum exposure period

Temperature

Minimum exposure period

70 °C or greater

1 second

66 °C

2 minutes

60 °C

32 minutes

Tables

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three B2V1.

Clauses referred to

Defined terms used