Verification Method · NCC 2025 Volume Three
B2V1 Heated water storage temperature
Part B2 Heated water services · NCC 2019: BV2.2
Compliance with B2P6 is verified for each heated water storage system when the water heater is designed such that all water is subjected to a temperature-dependent minimum exposure period as specified in Table B2V1 within 7 days before passing through the water-heating appliance's heated water outlet.
Table B2V1 Heated water storage minimum exposure period
Temperature
Minimum exposure period
70 °C or greater
1 second
66 °C
2 minutes
60 °C
32 minutes
Tables
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three B2V1.